Toshiba GR-200 Series Instruction Manual page 52

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Setting
2.1.8
OC_MV (Function ID: 440081)
Setting items
OC1-EN
OC2-EN
OC3-EN
OC4-EN
OC1
OC1-Dir
OC1-Angle
OC1-Timer
DT
OC1
OC1-DPR
TOC1
IEC
OC1
OC1-DPR
OC1-TMS-IEC
TOC1R
UK
OC1
OC1-DPR
OC1-TMS-UK
TOC1R
IEEE
OC1
OC1-DPR
OC1-TMS-
IEEE
OC1-Rtimer
TOC1R
OC1-RTMS-
IEEE
US
OC1
OC1-DPR
OC1-TMS-US
OC1-Rtimer
TOC1R
OC1-RTMS-US
ORG
OC1
OC1-DPR
OC1-TMS-ORG
OC1-Rtimer
TOC1R
OC1-RTMS-
ORG
OC1-k
OC1-a
OC1-c
OC1-kr
OC1-b
Output
OC1-2fBlk
Range
Unit
Off / On
- OC1 protection scheme switch
Off / On
- OC2 protection scheme switch
Off / On
- OC3 protection scheme switch
Off / On
- OC4 protection scheme switch
NonDir / Forward /
- OC1 directional characteristic
Reverse
-90 – 90
deg OC1 directional characteristic angle
DT / IEC-NI / IEC-VI /
IEC-EI / UK-LTI /
IEEE-MI / IEEE-VI /
- OC1 delay type
IEEE-EI / US-CO2 /
US-CO8 / Original
0.02 - 150.00
A OC1 threshold (in DT mode)
10 - 100
% OC1 drop-out/pick-up ratio
0.00 - 300.00
s OC1 operating delay time (in DT mode)
0.02 - 25.00
A OC1 threshold (in IDMT mode)
10 - 100
% OC1 drop-out/pick-up ratio
0.010 - 50.000
- OC1 time multiplier of IEC inverse curve
0.00 - 300.00
s OC1 definite time reset delay
0.02 - 25.00
A OC1 threshold (in IDMT mode)
10 - 100
% OC1 drop-out/pick-up ratio
0.010 - 50.000
- OC1 time multiplier of UK inverse curve
0.00 - 300.00
s OC1 definite time reset delay
0.02 - 25.00
A OC1 threshold (in IDMT mode)
10 - 100
% OC1 drop-out/pick-up ratio
0.010 - 50.000
- OC1 time multiplier of IEEE inverse curve
DEF / DEP
- OC1 reset delay type of IEEE
0.00 - 300.00
s OC1 definite time reset delay
OC1 dependent reset time multiplier of IEEE
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OC1 threshold (in IDMT mode)
10 - 100
% OC1 drop-out/pick-up ratio
0.010 - 50.000
- OC1 time multiplier of US inverse curve
DEF / DEP
- OC1 reset delay type of US
0.00 - 300.00
s OC1 definite time reset delay
OC1 dependent reset time multiplier of US
0.010 - 50.000
-
inverse curve
0.02 - 25.00
A OC1 threshold (in IDMT mode)
10 - 100
% OC1 drop-out/pick-up ratio
0.010 - 50.000
- OC1 time multiplier of ORG inverse curve
DEF / DEP
- OC1 reset delay type of US
0.00 - 300.00
s OC1 definite time reset delay
OC1 dependent reset time multiplier of ORG
0.010 - 50.000
-
inverse curve
0.00000 - 500.00000
- OC1 user original curve coefficient
0.00000 - 10.00000
- OC1 user original curve coefficient
0.00000 - 10.00000
- OC1 user original curve coefficient
0.00000 - 500.00000
- OC1 user original curve coefficient
0.00000 - 10.00000
- OC1 user original curve coefficient
Non / Block-AllP /
- OC1 operation block by 2f-detection
Block-PerP
- 33 -
Contents
6F2T0200 (0.15)
Default
Note
Off
Off
Off
Off
NonDir
-45
DT
1.00
100
1.00
1.00
100
1.000
0.00
1.00
100
1.000
0.00
1.00
100
1.000
DEF
0.00
1.000
1.00
100
1.000
DEF
0.00
1.000
1.00
100
1.000
DEF
0.00
1.000
0.00000
0.00000
0.00000
0.00000
0.00000
Non
GRE200 (1,2)