Advertisement

5. Counter limit:
6. Quality signal:
made, the selection will be canceled automatically after the setting
time [EXEWAIT] if the control result is not received at the IED from
the target device. The setting time ranges from 30 to 300sec. in 1
sec. steps.
The maximum value of the counters can be set between 9 and
2,147,483,647 using [CNTVALMAX]. The default setting is 999,999.
If "q" or "Quality" information shall not be taken for controlling, set
On for setting [QBLK]. The QBLK clears the content of quality
information, so that control operation can be achieved with the
absence of quality information.
- 417 -
6F2T0200 (0.15)
GRE200 (1,2)