CB decision logic
(iii)
Figure 2.24-1 shows the decision logic of the PROT_COMMON and outputs the decision state
of the CB: CB-A_CLOSE, CB-B_CLOSE, and others.
For the operation, the user should inject signals of CB states for the following PLC
connection points: 'CB1-A NO CONT', 'CB1-A NC CONT' and others. Note that a common point
is ready for the CB designed to three-phase tripping: CB1-NO CONT' and 'CB1-NC CONT'.
800000EBB0 CB1-A_NO_CONT
800000EBB7 CB1-A_NC_CONT
810000EBB1 CB1-B_NO_CONT
810000EBB8 CB1-B_NC_CONT
820000EBB2 CB1-C_NO_CONT
820000EBB9 CB1-C_NC_CONT
830000EBBE CB1-NO_CONT
830000EBBF CB1-NC_CONT
≥1
NO
≥1
NC
Both
CB-Contact
On
CB-SV
Figure 2.24-1 CB decision logic with supervision feature
8000001BB0
≥1
8300001BBE
1
=1
8000001B87
≥1
8300001BBF
8100001BB1
≥1
8300001BBE
1
=1
8100001B88
≥1
8300001BBF
8200001BB2
≥1
8300001BBE
8200001B89
1
=1
≥1
8300001BBF
&
&
≥1
≥1
1
≥1
&
≥1
&
≥1
≥1
1
&
&
≥1
≥1
1
≥1
&
- 273 -
TCBSV
t
0
&
0–100S
TCBSV
t
0
&
0–100S
TCBSV
t
0
&
0–100S
≥1
8000001B73
8000001B74
8000001B75
8000001B76
&
8000001B77
1
&
8000001B78
8700001B8F
1
8000001B79
1
8000001B7A
&
≥1
1
6F2T0200 (0.15)
8000001B93
CB1-A_FAIL
8100001B94
CB1-B_FAIL
8200001B95
CB1-C_FAIL
8300001B96
CB1-FAIL
8000001B88
CB-A_CLOSE
8100001B89
CB-B_CLOSE
8200001B8A
CB-C_CLOSE
To ARC
8300001B8B
CB-ALLPH_CLOSE
To VTF, CTF
CB-ALLPH_CLOSE
CB-ALLPH_OPEN
To CLP
CB-ALLPH_OPEN
8800001B90
≥1
CB-ANYPH_CLOSE
8500001B8C
CB-A_OPEN
8500001B8D
CB-B_OPEN
8600001B8E
CB-C_OPEN
To Dead-line
detection logic
8700001B8F
CB-ALLPH_OPEN
&
To OVG, OVN
TCBLOSPH
8900001B91
t
0
≥1
CB-LOSS_PHASE
0.00 to 0.10s
GRE200 (1,2)