Toshiba GR-200 Series Instruction Manual page 344

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

(iv)-2○
2
We cannot simply determine the finished start-up status by observing the motor
current. Therefore, it is possible to define by the setting [Mot-Start-IrrMode2],
whether the motor status is to be continued "Start-up" or change to "Running",
when the motor start-up time elapses.
b. Motor status transition for setting [Mot-Start-IrrMode2]=ChangeRun
Figure 2.28-5.a illustrates the motor status transition when ContStart is set for
the setting [Mot-Start-IrrMode2]. Even if the motor start-up time elapses, the
motor status is continued "Start-up".
b. Motor status transition for setting [Mot-Start-IrrMode2]=ChangeRun
Figure 2.28-5.b illustrates the motor status transition when ChangeRun is set for
the setting [Mot-Start-IrrMode2]. After the motor start-up time has elapsed, the
motor status is changed to "Running".
Motor current
Motor rated current
× 1.5
Overload current
Motor rated current
Motor rated current
× 0.05
a. Motor status transition for setting [Mot-Start-IrrMode2]=ContStart
Motor current
Motor rated current
× 1.5
Overload current
Motor rated current
Motor rated current
× 0.05
b. Motor status transition for setting [Mot-Start-IrrMode2]=ChangeRun
Figure 2.28-5 Motor status transitions in irregular mode-2B
Irregular mode-2B: In case of the motor current falls below 150% of [Mot-Ir]
Motor protection started
Motor protection started
Motor start-up time
Start-up
Motor start-up time
Start-up
- 325 -
6F2T0200 (0.15)
Stop
Running
Stop
GRE200 (1,2)
Time
Time