Toshiba GR-200 Series Instruction Manual page 203

Multi functional protection ied
Hide thumbs Also See for GR-200 Series:

Advertisement

Setting of OVS_MV (Function ID: 461181)
Setting device
OVS4-DPR
OVS4-TMS
TOVS4R
ORG
OVS4
OVS4-DPR
OVS4-TMS
TOVS4R
Output
OVS4-VTFBlk
OVS4-UseFor
Range
Unit
10 - 100
% OVS4 drop-out/pick-up ratio
0.010 - 100.000
- OVS4 time multiplier (in IDMT mode)
0.0 - 300.0
s OVS4 definite time reset delay
1.0 - 220.0
V OVS4 threshold
10 - 100
% OVS4 drop-out/pick-up ratio
0.010 - 100.000
- OVS4 time multiplier (in ORG mode)
0.0 - 300.0
s OVS4 definite time reset delay
Non / Block
- OVS4 operation block by VTF
Trip / Alarm
- OVS4 used for trip or alarm
- 184 -
Contents
6F2T0200 (0.15)
Default
Note
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
GRE200 (1,2)