FRQ_MV(Function ID: 475181)
Setting items
DFRQ1
Output
DFRQ1-UseFor
DFRQ2
DFRQ2-Chara
DFRQ2
Output
DFRQ2-UseFor
DFRQ3
DFRQ3-Chara
DFRQ3
Output
DFRQ3-UseFor
DFRQ4
DFRQ4-Chara
DFRQ4
Output
DFRQ4-UseFor
DFRQ5
DFRQ5-Chara
DFRQ5
Output
DFRQ5-UseFor
DFRQ6
DFRQ6-Chara
DFRQ6
Output
DFRQ6-UseFor
DFRQ7
DFRQ7-Chara
DFRQ7
Output
DFRQ7-UseFor
DFRQ8
DFRQ8-Chara
DFRQ8
Output
DFRQ8-UseFor
RCD
FRQ-RCD
FRQ-RCD-AR-
OF
FRQ-RCD-AR-
UF
Range
Unit
0.1 - 15.0
DFRQ1 threshold
Hz/s
Trip / Alarm
- DFRQ1 used for trip or alarm
Rise / Down
- The selection of DFRQ2 character
0.1 - 15.0
DFRQ2 threshold
Hz/s
Trip / Alarm
- DFRQ2 used for trip or alarm
Rise / Down
- The selection of DFRQ3 character
0.1 - 15.0
DFRQ3 threshold
Hz/s
Trip / Alarm
- DFRQ3 used for trip or alarm
Rise / Down
- The selection of DFRQ4 character
0.1 - 15.0
DFRQ4 threshold
Hz/s
Trip / Alarm
- DFRQ4 used for trip or alarm
Rise / Down
- The selection of DFRQ5 character
0.1 - 15.0
DFRQ5 threshold
Hz/s
Trip / Alarm
- DFRQ5 used for trip or alarm
Rise / Down
- The selection of DFRQ6 character
0.1 - 15.0
DFRQ6 threshold
Hz/s
Trip / Alarm
- DFRQ6 used for trip or alarm
Rise / Down
- The selection of DFRQ7 character
0.1 - 15.0
DFRQ7 threshold
Hz/s
Trip / Alarm
- DFRQ7 used for trip or alarm
Rise / Down
- The selection of DFRQ8 character
0.1 - 15.0
DFRQ8 threshold
Hz/s
Trip / Alarm
- DFRQ8 used for trip or alarm
5.0 - 30.0
FRQ Rapid Change Detector
Hz/s
FRQ Rapid Change Detector Active Area For
0.00 - 10.00
Hz
OF
FRQ Rapid Change Detector Active Area For
-10.00 - 0.00
Hz
UF
- 217 -
Contents
6F2T0200 (0.15)
Default
Note
0.5
Trip
Down
0.5
Trip
Down
0.5
Trip
Down
0.5
Trip
Down
0.5
Trip
Down
0.5
Trip
Down
0.5
Trip
Down
0.5
Trip
20.0
1.00
-1.00
GRE200 (1,2)