MOT_MV (Function ID: 4C2081)
Setting items
Mot-EN
Mot-Ir
Mot-Itype
Mot-Itype-q
Motor status
T-Mot-Start
Irregular
Mot-Start-IrrMode1
mode
Mot-Start-IrrMode2
Mot-Start-IrrOp
Motor start
Mot-StPro-EN
protection
T-Mot-StPro
Thermal overload
Mot-THMT-EN
protection
Mot-THMA-EN
Mot-THM
T-Mot-THM
T-Mot-THM-rad
Mot-THM-Alarm
Stalled motor
Mot-Stall-EN
protection
Mot-Stall-OC
T-Mot-Stall
Locked rotor
Mot-LKRT-EN
protection
Mot-LKRT
Mot-LKRT-IS
T-Mot-LKRT
Restart
Thermal
inhibit
state of
Mot-THSR-EN
function
rotor
Starts
Mot-STPH-EN
per hour
Mot-STPH-Num
Range
Unit
Off / On
-
Motor protection function enable
0.20 - 10.00
A Motor rated current
Max phase /
Selection of current for motor protection
-
Equivalent
judgment
-
0 - 10
Factor q value in [Mot-Itype]=Equivalent
0.10 - 300.00
s
Motor start-up time
ContStart /
Definition of mode change in irregular
-
ChangeRun
mode-1
ContStart /
Definition of mode change in irregular
-
ChangeRun
mode-2
Off / On-Trip /
Operation mode when the Start-up state
-
On-Alarm
continues in irregular mode
Off / On
-
Motor start protection enable
0.10 - 300.00
s
Time for motor start protection judgment
Off / On
-
Thermal trip protection enable
Off / On
-
Thermal alarm function enable
0.40 - 10.00
A Thermal overload current
Thermal time constant in generation of
0.5 - 500.0
min
heat
0.5 - 500.0
min Thermal time constant in radiation state
Thermal alarm level multiplier
50 - 100
%
(Rate of [Mot-THM] setting)
Off / On
-
Stalled motor protection enable
Overcurrent threshold of stalled motor
0.10 - 50.00
A
protection
Time for stalled motor protection
0.00 - 300.00
s
judgment
Off / On
-
Locked rotor protection enable
Thermal level multiplier
50 - 1000
%
(Rate of [Mot-THM] setting)
0.10 - 100.00
A Motor start-up current
1 - 300
s
Allowable locked rotor time
Off / On
-
Thermal state of rotor function enable
Off / On
-
Starts per hour function enable
1 - 60
-
Limit number for Starts per hour
- 344 -
6F2T0200 (0.15)
Contents
Equivalent
ContStart
ContStart
On-Alarm
GRE200 (1,2)
Default
Note
Off
1.00
0
60.0
Off
Off
Off
Off
1.00
10.0
10.0
80
Off
5.00
1.00
Off
200
7.50
120
Off
Off
60