Figure 4.1-51 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point "DPOS01_OSL_BO_FLG" is actually chosen for the
setting [DPOS01-OSLBORD]; i.e. BO1-RB is not chosen for this selection. This special setting
can issue a select command, which is called "operated by internal select function". The user
does not need to consider the use of a BO circuit for a select command, when there are no BIO
circuits available.
Table 4.1-30 Extra setting example for contact health check
Example #3
"DPOS01_OSL_BO_FLG" is not connected to any "BO"
"DPOS01_FSL_BO_FLG" is not connected to any "BO"
"DPOS01_OEX_BO_CSF" is connected to "BO3" at IO#1-2
"DPOS01_FEX_BO_CSF" is connected to "BO4" at IO#1-2
Remote/Local-end
" DPOS01_OSL_BO_FLG "
(512001 8603011DC6)
Select command On
" DPOS01_FSL_BO_FLG "
(512001 8A03011DC4)
Select command Off
" DPOS01_OEX_BO "
(512001 8203011DD3)
Operate command On
" DPOS01_FEX_BO "
(512001 8103011DD0)
Operate command Off
Figure 4.1-51 Contact health check setting and 43SW scheme for example#3
Settings for extra contact health check (special setting, example #3)
" BO3-RB "
( 200B41_8202021113)
" BO4-RB "
( 200B41_8302031113)
Contact health check setting for example #3
"DPOS01_OSL_BO_FLG" set for [DPOS01-OSLBORD]
"DPOS01_OSL_BO_FLG" set for [DPOS01-FSLBORD]
200B41 8102011113(BO2-RB) set for [DPOS01-OEXBORD]
200B41 8202021113 (BO3-RB) set for [DPOS01-FEXBORD]
BIO module
Drivers
SW1 is not driven with any BO
Physical BOs
are virtualized.
SW2 is not driven with any BO
SW3 is driven with
BO3 at IO#1-2
BO3
SW4 is driven with
BO4 at IO#1-2
BO4
- 479 -
6F2T0200 (0.15)
43SW
Plus (+)
SW 1
On
command
SW 3
SW 2
Off
command
SW 4
Minus (−)
GRE200 (1,2)
OK
OK
OK
OK