Setting
2.13.5
Setting of UV_MV (Function ID: 470181)
Setting device
BLK
UVBLK
UVBLK
TUVBLK
UV1-EN
UV2-EN
UV3-EN
UV4-EN
UV1
UV1-Timer
DT
UV1
UV1-DPR
TUV1
IDMT
UV1
UV1-DPR
UV1-TMS
TUV1R
ORG
UV1
UV1-DPR
UV1-TMS
TUV1R
Output
UV1-VTFBlk
UV1-UseFor
UV2
UV2-Timer
DT
UV2
UV2-DPR
TUV2
IDMT
UV2
UV2-DPR
UV2-TMS
TUV2R
ORG
UV2
UV2-DPR
UV2-TMS
TUV2R
Output
UV2-VTFBlk
UV2-UseFor
UV3
UV3-Timer
DT
UV2
UV3-DPR
TUV3
IDMT
UV3
UV3-DPR
UV3-TMS
TUV3R
ORG
UV3
UV3-DPR
UV3-TMS
TUV3R
Output
UV3-VTFBlk
UV3-UseFor
UV4
UV4-Timer
DT
UV4
UV4-DPR
Range
Unit
Off / On
- Operation canceled when UVBLK operated
10.0
V Threshold of UVBLK element
10.00
S UVBLK operation delay timer
Off / On
- UV1 protection scheme switch
Off / On
- UV2 protection scheme switch
Off / On
- UV3 protection scheme switch
Off / On
- UV4 protection scheme switch
DT / IDMT / Original
- UV1 delay type
5.0 - 130.0
V UV1 threshold
100 – 120
% UV1 drop-out/pick-up ratio
0.00 - 300.00
s UV1 operating delay time (in DT mode)
5.0 - 130.0
V UV1 threshold
100 - 120
% UV1 drop-out/pick-up ratio
0.010 - 100.000
- UV1 time multiplier (in IDMT mode)
0.0 - 300.0
s UV1 definite time reset delay
5.0 - 130.0
V UV1 threshold
100 - 120
% UV1 drop-out/pick-up ratio
0.010 - 100.000
- UV1 time multiplier (in ORG mode)
0.0 - 300.0
s UV1 definite time reset delay
Non / Block
- UV1 operation block by VTF
Trip / Alarm
- UV1 used for trip or alarm
DT / IDMT / Original
- UV2 delay type
5.0 - 130.0
V UV2 threshold
100 - 120
% UV2 drop-out/pick-up ratio
0.00 - 300.00
s UV2 operating delay time (in DT mode)
5.0 - 130.0
V UV2 threshold
100 - 120
% UV2 drop-out/pick-up ratio
0.010 - 100.000
- UV2 time multiplier (in IDMT mode)
0.0 - 300.0
s UV2 definite time reset delay
5.0 - 130.0
V UV2 threshold
100 - 120
% UV2 drop-out/pick-up ratio
0.010 - 100.000
- UV2 time multiplier (in ORG mode)
0.0 - 300.0
s UV2 definite time reset delay
Non / Block
- UV2 operation block by VTF
Trip / Alarm
- UV2 used for trip or alarm
DT / IDMT / Original
- UV3 delay type
5.0 - 130.0
V UV3 threshold
100 - 120
% UV3 drop-out/pick-up ratio
0.00 - 300.00
s UV3 operating delay time (in DT mode)
5.0 - 130.0
V UV3 threshold
100 - 120
% UV3 drop-out/pick-up ratio
0.010 - 100.000
- UV3 time multiplier (in IDMT mode)
0.0 - 300.0
s UV3 definite time reset delay
5.0 - 130.0
V UV3 threshold
100 - 120
% UV3 drop-out/pick-up ratio
0.010 - 100.000
- UV3 time multiplier (in ORG mode)
0.0 - 300.0
s UV3 definite time reset delay
Non / Block
- UV3 operation block by VTF
Trip / Alarm
- UV3 used for trip or alarm
DT / IDMT / Original
- UV4 delay type
5.0 - 130.0
V UV4 threshold
100 - 120
% UV4 drop-out/pick-up ratio
- 150 -
Contents
6F2T0200 (0.15)
Default
Note
Off
10.0
10.00
Off
Off
Off
Off
DT
60.0
100
1.00
60.0
100
1.000
0.0
60.0
100
1.000
0.0
Non
Trip
DT
60.0
100
1.00
60.0
100
1.000
0.0
60.0
100
1.000
0.0
Non
Trip
DT
60.0
100
1.00
60.0
100
1.000
0.0
60.0
100
1.000
0.0
Non
Trip
DT
60.0
100
GRE200 (1,2)