Object_reference
Ctrl/CSWI1$Pos$origin
orCat
Ctrl/CSWI1$Pos$origin
orIdent
Ctrl/CSWI1$Pos
stVal
Ctrl/CSWI1$Pos
q
Ctrl/CSWI1$Pos
t
Ctrl/CSWI1$Pos
stSeld
Note: "Status (ST)" is defined in the function constraint (FC) of the IEC 61850.
Figure 4.1-55 orCat attribute mapped into DPC object of CSWI1
Mapping input data
(iii)
The DPSY01 function can receive three commands "select, operate and cancel." Thus, the user
should map the input-point "
4.1-39
shows
the
"Ctrl/CSWI1$Pos"
CO†.. Figure 4.1-56
†Note: The attribute is defined in the IEC 61850; "CO" stands for "Control" in the
functional constraint (FC).
Table 4.1-38 Mapping signals for CSWI1 object
Attribute
Type
orCategory
Octet64
Dbpos
Quality
Timestamp
BOOLEAN
DEV01_CONTROL_REQ" to the IEC 61850 configuration.
input-point
"DEV01_CONTROL_REQ"
; the user should map the input-point to the Object reference having
map a signal.
shows how to
- 478 -
FC
Signal Number
ST
511001 3102011008
ST
511001 6A02011009
ST
511001 3102011001
ST
511001 3102011005
ST
511001 9002011006
ST
511001 0002011D90
6F2T0207 (0.01)
Signal Name
DPSY01_3PH_ORCAT
DPSY01_3PH_ORIDENT
DPSY01_3PH_STATE
DPSY01_3PH_QUALITY
DPSY01_3PH_TIMESTAMP
DPSY01_STD_RPT
Drag and drop
and
the
Object
reference
attribute
GRE200 (5,6)
Table

Advertisement

loading