Setting of OV_MV (Function ID: 460181)
Setting device
OV4-DPR
OV4-TMS
TOV4R
ORG
OV4
OV4-DPR
OV4-TMS
TOV4R
Output
OV4-VTFBlk
OV4-UseFor
Range
Unit
10 - 100
% OV4 drop-out/pick-up ratio
0.010 - 100.000
- OV4 time multiplier (in IDMT mode)
0.0 - 300.0
s OV4 definite time reset delay
1.0 - 220.0
V OV4 threshold
10 - 100
% OV4 drop-out/pick-up ratio
0.010 - 100.000
- OV4 time multiplier (in ORG mode)
0.0 - 300.0
s OV4 definite time reset delay
Non / Block
- OV4 operation block by VTF
Trip / Alarm
- OV4 used for trip or alarm
- 173 -
Contents
6F2T0207 (0.01)
Default
Note
100
1.000
0.0
120.0
100
1.000
0.0
Non
Trip
GRE200 (5,6)