Download Print this page

Toshiba GR-200-5 Instruction Manual page 160

Multi functional protection ied

Advertisement

Setting
2.12.6
CBF_MV (Function ID: 453081)
Setting items
CBF-EN
OC
OCCBF-EN
OCCBF
EF
EFCBF-EN
EFCBF
Timer
TCBF-RE
TCBF-TP
Output
CBF-Retrip
CBF-Trip
Range
Unit
Off / On
- CBF protection scheme switch
Off / On
- Current flow is judged by OC relay operation
OCCBF relay operating level (Current flow
0.10 - 25.00
A
judgment)
Off / On
- Current flow is judged by EF relay operation
EFCBF relay operating level (Current flow
0.10 - 25.00
A
judgment)
0.000 - 300.000
s CBF retrip timer
0.000 - 300.000
s CBF trip timer
Off / On / On-T
- CBF retrip operation mode
Off / On / On-AftRe
- CBF trip operation mode
- 140 -
Contents
6F2T0207 (0.01)
Default
Note
Off
On
1.00
Off
1.00
0.150
0.200
On
On
GRE200 (5,6)