Download Print this page

Toshiba GR-200-5 Instruction Manual page 686

Multi functional protection ied

Advertisement

Table 5.6-8 Setting items for binary output circuits of IO#1
Setting of BIO_SLOT_MV (Function ID: 200B41)
Setting items
BO 1
BO1_CPL
CPL Input signal1
(Preferred Data ID)
Input signal2
(Preferred Data ID)
Input signal3
(Preferred Data ID)
Input signal4
(Preferred Data ID)
Input signal5
(Preferred Data ID)
Input signal6
(Preferred Data ID)
Input signal7
(Preferred Data ID)
Input signal8
(Preferred Data ID)
LOGIC-SW
AND / OR / XOR
On Delay Timer
0.000 - 300.000
Off Delay Timer
0.000 - 300.000
INVERSE-SW
Normal / Inverse
Off / Delay / Dwell
TIMER-SW
Logic Timer
0.000 - 300.000
Reset signal
(Preferred Data ID)
BO 2
BO2_CPL
CPL Input signal1
(Preferred Data ID)
Input signal2
(Preferred Data ID)
Input signal3
(Preferred Data ID)
Input signal4
(Preferred Data ID)
Input signal5
(Preferred Data ID)
Input signal6
(Preferred Data ID)
Input signal7
(Preferred Data ID)
Input signal8
(Preferred Data ID)
LOGIC-SW
AND / OR / XOR
On Delay Timer
0.000 - 300.000
Off Delay Timer
0.000 - 300.000
INVERSE-SW
Normal / Inverse
Off / Delay / Dwell
TIMER-SW
Logic Timer
0.000 - 300.000
Reset signal
(Preferred Data ID)
BO 3
BO3_CPL
CPL Input signal1
(Preferred Data ID)
Input signal2
(Preferred Data ID)
Input signal3
(Preferred Data ID)
Input signal4
(Preferred Data ID)
Input signal5
(Preferred Data ID)
Input signal6
(Preferred Data ID)
Input signal7
(Preferred Data ID)
Input signal8
(Preferred Data ID)
LOGIC-SW
AND / OR / XOR
On Delay Timer
0.000 - 300.000
Off Delay Timer
0.000 - 300.000
Range
Contents
Unit
Switch for programming on binary
Off / On
-
output circuit1
Data ID of the arrival signal at circuit
-
entrance#1
Data ID of the arrival signal at circuit
-
entrance#2
Data ID of the arrival signal at circuit
-
entrance#3
Data ID of the arrival signal at circuit
-
entrance#4
Data ID of the arrival signal at circuit
-
entrance#5
Data ID of the arrival signal at circuit
-
entrance#6
Data ID of the arrival signal at circuit
-
entrance#7
Data ID of the arrival signal at circuit
-
entrance#8
Selection of gate for arrival signals#1–
-
#8
Setting value for On-delay timer
s
s
Setting value for Off-delay timer
Switch to inverse a binary output
-
Selection of Logic circuit
-
/ Latch
Off delay timer value: "Delay" and
s
"Dwell" circuit
Reset signal selection for "Latch" circuit
-
Switch for programming on binary
Off / On
-
output circuit2
Data ID of the arrival signal at circuit
-
entrance#1
Data ID of the arrival signal at circuit
-
entrance#2
Data ID of the arrival signal at circuit
-
entrance#3
Data ID of the arrival signal at circuit
-
entrance#4
Data ID of the arrival signal at circuit
-
entrance#5
Data ID of the arrival signal at circuit
-
entrance#6
Data ID of the arrival signal at circuit
-
entrance#7
Data ID of the arrival signal at circuit
-
entrance#8
Selection of gate for arrival signals#1–
-
#8
s
Setting value for On-delay timer
Setting value for Off-delay timer
s
Switch to inverse a binary output
-
Selection of Logic circuit
-
/ Latch
Off delay timer value: "Delay" and
s
"Dwell" circuit
-
Reset signal selection for "Latch" circuit
Switch for programming on binary
Off / On
-
output circuit3
Data ID of the arrival signal at circuit
-
entrance#1
Data ID of the arrival signal at circuit
-
entrance#2
Data ID of the arrival signal at circuit
-
entrance#3
Data ID of the arrival signal at circuit
-
entrance#4
Data ID of the arrival signal at circuit
-
entrance#5
Data ID of the arrival signal at circuit
-
entrance#6
Data ID of the arrival signal at circuit
-
entrance#7
Data ID of the arrival signal at circuit
-
entrance#8
Selection of gate for arrival signals#1–
-
#8
Setting value for On-delay timer
s
Setting value for Off-delay timer
s
GRE200-5
On
440081 8000011B23
441081 8000011B23
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
OR
0.000
0.000
Normal
Off
0.000
Not assigned
On
440081 8000021B23
441081 8000021B23
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
OR
0.000
0.000
Normal
Off
0.000
Not assigned
On
460181 8000011B23
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
AND
0.000
0.000
- 666 -
6F2T0207 (0.01)
Default
GRE200-6
Note
On
OC1-OPT-
440081 8000011B23
TRIP
EF1-OPT-
442081 8000011B23
TRIP
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
OR
0.000
0.000
Normal
Off
0.000
Not assigned
On
OC2-OPT-
440081 8000021B23
TRIP
EF2-OPT-
44208 18000021B23
TRIP
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
OR
0.000
0.000
Normal
Off
0.000
Not assigned
On
OV1-OPT-
460181 8000011B23
TRIP
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
Not assigned
AND
0.000
0.000
GRE200 (5,6)
Note
OC1-OPT-
TRIP
SEF1-OPT-
TRIP
OC2-OPT-
TRIP
SEF2-OPT-
TRIP
OV1-OPT-
TRIP

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6