10.2.35 Supervision of board connection (Board error)
This supervises, as it were, whether a module is properly connected (i.e., supervising the
connection of MV-BI* module, mainly. This is because the MV-BI* have binary inputs, but does
not have output circuit [except for the alarm output of fail]. See p. 651, 653, 654). Sending and
receiving signals between HMI-VCT-CPU-BIO modules are monitored by this, and a
connection error will be judged if those signals for sending and receiving are interrupted.
†Note:MV-BI3 (See p.) and MV-BI4 (See p.) are same as MV-BI1.
Error level
(i)
The error level has been set at level 1 (Serious error) in the automatic supervision. Checking
errors is carried out at any time. The manufacturer has set one second to detect a failure. The
error will be reset within a second when the failure is solved.
Error message
(ii)
When detecting an error, the error message will be shown on the LCD screen. LED will be lit
up.
Table 10.2-71 Error messages by the supervision of board connection (CHK_BOARD_CONN)
Message and level
BOARD(CONN) error
Error level
Table 10.2-72 Detailed information in the supervision of board connection (CHK_BOARD_CONN)
Display
area
Top
00000001: Board connection error
row
Middle
(No message displayed)
row
Bottom
(No message displayed)
row
Meaning of the information
Detection of the board connection error
Serious error (Level 1)
Meaning of the detailed information
Left column
- 839 -
6F2T0207 (0.01)
Right column
(No message displayed)
(No message displayed)
(No message displayed)
GRE200 (5,6)