Multi functional protection ied

Advertisement

Control logics for SBO/DIR modes
4.3.5
Control logics for 'HHD resetting and 'VAR resetting' are provided.
Receiving "Select command for HHD resetting" from the remote-end
(i)
Figure 4.3-9 shows the logic when a "Select command (Remote-RESET-Control)" signal is
applied in HHD control. The logic has an input-point "PWRQ_HHD_RSTREQ" for the
reception of the select command; the point should be mapped for the IEC61850 communication
(see sec. 4.3.8). The input-point "PWRQ_HHD_RSTREQ" is significant to HHD resetting; the
HHD failure will be indicated if mapping is not performed correctly.
Input
Command "Remote-On-Control"
543081 7019016D08
PWRQ_HHD_RSTREQ
Either "SBO mode" or "DIR mode"
(e.g., "ctlmodel" in IEC61850*)
‡Note: "Select condition" signal is provided from select condition scheme. For more
information, see Figure 4.3-10.
*Note: The PWRQTY function can run on either the "SBO mode" or the "DIR mode". The
user can use the signal "ctlmodel" in the IEC61850 communication.
Select condition for HHD resetting
(ii)
Figure 4.3-10 shows the select condition logic of HHD resetting. The logic examines an operate-
condition using "Command Blocking" signal
PWRQTY function (Function ID: 543081)
For SBO operation
Select command
For DIR operation
Operate command
In SBO operate
In DIR operate
Select condition‡
Figure 4.3-9 Select logic for 'HHD resetting'
- 564 -
510001 7001016D08
Select logic in PWRQTY
1≥
&
&
.
1
6F2T0207 (0.01)
Output
&
HDD_SE_RCV
543081 8519011E45
0
t
Select "success"
0.1s
To "Wait for a command"
t
0
Select "Failed"
0.6s
GRE200 (5,6)