should set V3 for both scheme switches [SyncRy1-VR] and [SyncRy2-VR], respectively. The
incoming voltage (V I ) is provided by the Line voltage (V1), therefore either V-L1, V-L2, or V-L3
can be set for scheme switches [SyncRy1-VI] and [SyncRy2-VI]. Table 4.5-7 shows the setting
example for this arrangement.
Setting Name
Description
SyncRy1-VR
Selection of running voltage
SyncRy1-VI
Selection of incoming voltage
SyncRy2-VR
Selection of running voltage
SyncRy2-VI
Selection of incoming voltage
Table 4.5-7 Settings in Example1
- 616 -
Default
Setting item or value
V3
Either V3
V-L1
Either V-L1 / V-L2 / V-L3
V3
Either V3
V-L2
Either V-L1 / V-L2 / V-L3
6F2T0207 (0.01)