Download Print this page

Toshiba GR-200-5 Instruction Manual page 605

Multi functional protection ied

Advertisement

Nodes and formulae for interlock-check
(ii)
Figure 4.4-4 illustrates that an interlock-check is realized by using a number of nodes. For
each node, the user is required to configure input signals, interlock-operators, and links
between nodes. Following that, an interlock-check can be run.
Input A
Input B
Input C
Input D
Input E
Input F
Input G
Input H
Input I
Input J
Signal monitoring point
Figure 4.4-4 Operation of interlock-check
We can see that equation (4.4-10) is a representation of Figure 4.4-4. This equation is computed
in accordance with the priority order of the interlock-operators: the first is parentheses [()], the
second is AND [•], followed by OR [+].
Output = ((A+B) •C) + (D+E•F) + (G•(H+I) •J)
Node #1
OR (+)
Node #3
AND(• )
Node #5
OR (+)
Users can see signals at signal monitoring
points using the GR -TIE MS.
- 585 -
Node #2
AND(• )
Node #4
OR (+)
Node #6
AND(• )
6F2T0207 (0.01)
Node #7
AND(• )
Output
Users can see
signals by IED
screens.
(4.4-10)
GRE200 (5,6)

Advertisement

loading

This manual is also suitable for:

Gr-200 seriesGr-200-6