Multi functional protection ied

Advertisement

Signal monitoring points about Voltage variation
PWRQTY (FunctionID:543081)
Element ID
Name
8B19921EB8
Vs_INT_BLOCK
8D19921EB9
Vs_INT_STAGE3
8F19921EBA
Vs_INT_DETECTED
4201AB1076
SWL_V1ab_PEAK_PRI
4201BC1078
SWL_V1bc_PEAK_PRI
4201CA107A
SWL_V1ca_PEAK_PRI
4203001076
SWL_Vs_PEAK_PRI
3201AB1098
SWL_Vab_DURATION
3201BC1098
SWL_Vbc_DURATION
3201CA1098
SWL_Vca_DURATION
3203001098
SWL_Vs_DURATION
9001AB1006
SWL_Vab_TIMESTAMP
9001BC1006
SWL_Vbc_TIMESTAMP
9001CA1006
SWL_Vca_TIMESTAMP
9003001006
SWL_Vs_TIMESTAMP
4201AB1076
DIP_Vab_PEAK_PRI
4201BC1078
DIP_Vbc_PEAK_PRI
4201CA107A
DIP_Vca_PEAK_PRI
4203001076
DIP_Vs_PEAK_PRI
3201AB1098
DIP_Vab_DURATION
3201BC1098
DIP_Vbc_DURATION
3201CA1098
DIP_Vca_DURATION
3203001098
DIP_Vs_DURATION
9001AB1006
DIP_Vab_TIMESTAMP
9001BC1006
DIP_Vbc_TIMESTAMP
9001CA1006
DIP_Vca_TIMESTAMP
9003001006
DIP_Vs_TIMESTAMP
4201AB1076
INTRPT_Vab_PEAK_PRI
4201BC1078
INTRPT_Vbc_PEAK_PRI
4201CA107A
INTRPT_Vca_PEAK_PRI
4203001076
INTRPT_Vs_PEAK_PRI
3201AB1098
INTRPT_Vab_DURATION
3201BC1098
INTRPT_Vbc_DURATION
3201CA1098
INTRPT_Vca_DURATION
3203001098
INTRPT_Vs_DURATION
9001AB1006
INTRPT_Vab_TIMESTAMP
9001BC1006
INTRPT_Vbc_TIMESTAMP
9001CA1006
INTRPT_Vca_TIMESTAMP
9003001006
INTRPT_Vs_TIMESTAMP
Mapping points about Harmonics measurement
PWRQTY (FunctionID:543081)
Element ID
Name
42000F1095
THD_Ia
42000F1096
THD_Ib
42000F1097
THD_Ic
42100F1095
THD_Va
42100F1096
THD_Vb
42100F1097
THD_Vc
42300F1095
THD_Vs
4200101095
TDDa
4200101096
TDDb
Description
Interruption Vs(BLOCKING)
Interruption Vs(stage-3)
Interruption Vs(detected)
Peak value of Vab during swell for mapping
Peak value of Vbc during swell for mapping
Peak value of Vca during swell for mapping
Peak value of Vs during swell for mapping
Duration of Vab during swell(ms) for mapping
Duration of Vbc during swell(ms) for mapping
Duration of Vca during swell(ms) for mapping
Duration of Vs during swell(ms) for mapping
Detection time of swell for mapping
Detection time of swell for mapping
Detection time of swell for mapping
Detection time of swell for mapping
Peak value of Vab during dip/sag for mapping
Peak value of Vbc during dip/sag for mapping
Peak value of Vca during dip/sag for mapping
Peak value of Vs during dip/sag for mapping
Duration of Vab during dip/sag(ms) for mapping
Duration of Vbc during dip/sag(ms) for mapping
Duration of Vca during dip/sag(ms) for mapping
Duration of Vs during dip/sag(ms) for mapping
Detection time of dip/sag for mapping
Detection time of dip/sag for mapping
Detection time of dip/sag for mapping
Detection time of dip/sag for mapping
Peak value of Vab during interruption for mapping
Peak value of Vbc during interruption for mapping
Peak value of Vca during interruption for mapping
Peak value of Vs during interruption for mapping
Duration of Vab during interruption(ms) for mapping
Duration of Vbc during interruption(ms) for mapping
Duration of Vca during interruption(ms) for mapping
Duration of Vs during interruption(ms) for mapping
Detection time of interruption for mapping
Detection time of interruption for mapping
Detection time of interruption for mapping
Detection time of interruption for mapping
Description
Total harmonics distortion of Ia for mapping
Total harmonics distortion of Ib for mapping
Total harmonics distortion of Ic for mapping
Total harmonics distortion of Va for mapping
Total harmonics distortion of Vb for mapping
Total harmonics distortion of Vc for mapping
Total harmonics distortion of Vs for mapping
Total demand distortion of Ia for mapping
Total demand distortion of Ib for mapping
- 577 -