Toshiba GR-200-5 Instruction Manual page 297

Multi functional protection ied

Advertisement

Setting
2.24.6
PROT_COMMON_MV (Function ID: 48A081)
Setting items
UVLS
UVLG
OCD
CB-Contact
TCBLOSPH
CB-SV
TCBSV
DS-Contact
DS-SV
TDSSV
DLDbyUV
DLDbyCB
TDLD
UserLogicSW1
UserLogicSW2
UserLogicSW3
UserLogicSW4
Range
Unit
5.0 - 130.0
V UV phase-phase relay operating value
5.0 - 130.0
V UV phase-ground relay operating value
0.05 - 1.00
A OCD relay operating value
NO / NC / Both
- Kind of injected CB contact
0.00 - 0.10
s CB loss phase time
Off / On
- CB contact supervisor enable
0 - 100
s CB contact supervisor time
NO / NC / Both
- Kind of injected DS contact
Off / On
- DS contact supervisor enable
0 - 100
s DS contact supervisor time
Off / On
- Dead line detection by under voltage
Off / On
- Dead line detection by CB open
0.00 - 300.00
s Dead line detection timer
S1 / S2 / S3
- User Logic Switch1 for General purpose
S1 / S2 / S3
- User Logic Switch2 for General purpose
S1 / S2 / S3
- User Logic Switch3 for General purpose
S1 / S2 / S3
- User Logic Switch4 for General purpose
- 277 -
Contents
6F2T0207 (0.01)
Default
Note
77.0
45.0
0.10
NO
0.03
Off
10
NO
Off
60
Off
Off
10.00
S1
S1
S1
S1
GRE200 (5,6)