Figure 4.1-38 shows a setting example for an improper setting of the 43SW scheme. The
settings are implemented incorrectly, as shown in Table 4.1-23.
instead BO1 is actually chosen. In this case, the setting [SPOS01-SLBORD] is meaningless;
hence, the issue of a select command is blocked.
Table 4.1-23 Erroneous setting example for contact health check
Example #2
"SPOS01_SL_BO_FLG" is connected to "BO1" at IO#1
"SPOS01_OEX_BO_CSF" is connected to "BO2" at IO#1
"SPOS01_FEX_BO_CSF" is connected to "BO3" at IO#1
Remote/Local-end
"
SPOS01_SL_BO_FLG
(510001_8501011F76)
Select
Command
ON/OFF
"
SPOS01_OEX_BO
(510001_8201011DD3)
Operate-On
command
"
SPOS01_FEX_BO
(510001_8101011DD0)
Operate-Off
command
Figure 4.1-38 Contact health check setting and 43SW diagram for example #2
Figure 4.1-39 shows an additional setting example for the 43SW scheme; one of the settings is
made hypothetically. That is, the point "SPOS01_SL_BO_FLG" is actually chosen for the
setting [SPOS01-SLBORD]; i.e. BO1-RB is not chosen for this selection. This special example
can issue a select command; which is called "operated by internal select function". The user
does not need to consider of a BO circuit for a select command, when there are no BO circuits
available.
Table 4.1-24 Extra setting example for contact health check
Example #3
"SPOS01_SL_BO_FLG" is not connected to any "BO"
"SPOS01_OEX_BO_CSF" is connected to "BO2" at IO#1
"SPOS01_FEX_BO_CSF" is connected to "BO3" at IO#1
"BO1" (not BO1-RB)
"
mistakenly chosen with
"200B01_8002001112"
"
"
BO2-RB
"
"200B01_8102011113"
"
BO3-RB
"200B01_8202021113"
Setting for extra contact health check (special setting, example #3)
Health check setting in example #2
200B01 8002001112(BO1) set for [SPOS01-SLBORD]
200B01 8102011113(BO2-RB) set for [SPOS01-OEXBORD]
200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD]
BIO module
SW1 driven with
BO1at IO_SLOT1
BO1
SW2 driven with
BO2
BO2 at IO_SLOT1
"
designated with
SW3 driven with
BO3
BO3 at IO_SLOT1
"
designated with
Setting for example #3
"SPOS01_SL_BO_FLG" set for [SPOS01-SLBORD]
200B01 8102011113(BO2-RB) set for [SPOS01-OEXBORD]
200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD]
- 537 -
6F2S1915 (0.46)
BO1-RB is not chosen,
43SW
Plus (+)
SW 1
On
SW 2
Command
SW 3
Off
Command
Minus (−)
GRZ200 (Soft 031 & 032)
NG
OK
OK
OK
OK
OK