ARC1 and ARC2 functions being generating 'ARC1 IN-PROG OR' or 'ARC2-S1 IN-PROG'
signals. The switch [FT-3P FAULT] requires signals of the external relay; PLC connection
points 'RYOP-A, RYOP-B, and RYOP-C' are used to get the signals.
Note that the 'CB1_94TT' and 'CB2_94TT' signals are generated when 'ARC BLOCK'
signals are injected, provided 'ARC1 IN-PROG OR' or 'ARC2-S1 IN-PROG' signals is being
generated.
If, with regard to the tripped poles of CBs, there is not consistency between the CB#1 and
the CB#2, the ARC function can generate the 'CB1_94TT' and 'CB2_94TT' signals when an
external device is able to detect the consistency; use PLC connection points 'F.CB1_94TT' and
'F.CB2_94TT' for the operation of the inconsistency.
The Start logic can receive a stop signal not to operate the ARC function; use PLC
connection point 'ARC NO ACT'.
- 359 -
6F2S1915 (0.46)
GRZ200 (Soft 031 & 032)