Voltage selection for line arrangement
4.6.6
As shown in Figure 4.6-16, input-voltage signals are required in response to the line and bus-
bar arrangement. Incidentally, the input-voltage signals supplied by the VTs are applied to the
IED via the transformer module (VCT†); hence, the input-voltage signal should correspond
with the required relay-element. On this account, settings are provided in the SYNCHK_Ry
function.
Signal
names
VCT
Figure 4.6-18 Voltage signals selected using scheme switches
†Note: For the actual terminal arrangement and signals injected, see chapter
description: Transformer module for AC analog input.
Figure 4.6-18 illustrates that the signals injected are distributed using scheme switches:
[SyncRy1-VR], [SyncRy1-VI], [SyncRy1-VR], and [SyncRy1-VI]. Examples below show how to
apply a voltage signal for the required relay-element.
Setting example
(i)
Figure 4.6-19 depicts an example of a busbar arrangement and S43P logic programmed by the
user. In this case, only the SYNCHK_Ry1 function is used; therefore, the user need only select
the signal provided by the S43P logic for the SYNCHK_Ry1 function.
Setting
names
Va
V-L1
Vb
V-L2
Vc
V-L3
Scheme switches [SyncRy1-VR] etc. select a running
Vs
V3
Vs2
V4
Scheme switches [SyncRy2-VR] etc. select a running
- 694 -
SYNCHK_ Ry1
Relays for
running voltage
Relays for
incoming voltage
voltage and an incoming voltage.
SYNCHK_ Ry2
Relays for
running voltage
Relays for
incoming voltage
voltage and an incoming voltage.
6F2S1915 (0.46)
Technical
GRZ200 (Soft 031 & 032)
V2a
V2b
V2c

Advertisement

loading

This manual is also suitable for:

Grz200