Download Print this page

Toshiba GR200 Series Instruction Manual page 557

Hide thumbs Also See for GR200 Series:

Advertisement

Similarly, the point "BO3-RB" must be applied for the setting [SPOS01-FEXBORD].
Figure 4.1-36 Example connection of "Operate command off" for the health check feature
Figure 4.1-37 shows a setting example for the 43SW scheme. Select and operate commands
drive the BO1, BO2 and BO3 contacts. To check that the contact health check function is
working correctly, the respective points of the BO-RBs should be connected as shown in Table
4.1-22, to demonstrate that the settings are physically matched with the BO contacts.
Example #1
"SPOS01_SL_BO_FLG" is connected to "BO1" at IO#1
"SPOS01_OEX_BO_CSF" is connected to "BO2" at IO#1
"SPOS01_FEX_BO_CSF" is connected to "BO3" at IO#1
Remote/Local-end
"
SPOS01_SL_BO_FLG
(510001_8501011F76)
Select
command ON/OFF
"
SPOS01_OEX_BO
(510001_8201011DD3)
Operate-On
command
"
SPOS01_FEX_BO
(510001_8101011DD0)
Operate-Off
command
Figure 4.1-37 Contact health check setting and 43SW scheme for example #1
Operate-Off command check
Operate logic in
SPOS01
"
"
SPOS01_FEX_BO
"510001_8101011DD0"
BO3 circuit at
IO_#1
"
"
BO3-RB
"200B01_8102021113"
setting [SPOS01-FEXBORD]
Connection made by the user
Proper setting for the contact health check (normal setting, example #1)
Table 4.1-22 Setting example for contact health check
"
"
BO1-RB
(
200B01_8002001113)
"
"
BO2-RB
(
200B01_8102011113)
"
"
BO3-RB
(
200B01_8202021113)
Setting for erroneous contact health check (improper setting, example #2)
Contact health check
logic in SPOS01
Result of contact
health check
&
Signal designated by
Health check setting for Example #1
200B01 8002001113(BO1-RB) set for [SPOS01-SLBORD]
200B01 8102011113(BO2-RB) set for [SPOS01-OEXBORD]
200B01 8202021113 (BO3-RB) set for [SPOS01-FEXBORD]
BIO module
Drivers
SW1 driven with
BO1 at IO_SLOT1
BO1
"
BO2
SW2 driven with
BO2 at IO_SLOT1
"
SW3 driven with
BO3
BO3 at IO_SLOT1
"
- 536 -
6F2S1915 (0.46)
43SW
Plus (+)
SW 1
On
SW 2
Command
SW 3
Off
Command
Minus (−)
GRZ200 (Soft 031 & 032)
OK
OK
OK

Advertisement

loading

This manual is also suitable for:

Grz200