4.2.6(i)-3)
Note: A supervision of the Binary IO module can detect connection errors for BI circuits
7
Note: The "Common control" (CMNCTRL) function can test and check the operation-
8
direction of logic. When the user sets Off for scheme switch [SCDEN], operation of
the logic is blocked if the logic is running in the same operation-direction
compared with the previous operation-direction. Alternatively, if On is set for the
scheme switch, the logic is not blocked.
Note: The user must program the PLC logic for "Control hierarchy condition". The user
9
must connect the "Control hierarchy condition" to the select condition logic using
the connection point "DPSY01IN_TMP_28". For more information, see Chapter
Control and monitoring application: Control hierarchy
Note that the logic outputs are generated separately for both the Closing-
execution and the Open-execution.
Signal name and number
(viii)
Note: The user should note the meaning of the following abbreviations shown in column
"M/O" of each table:
"O" signifies that the signal is provided for optional use.
"M" signifies that the user should map/set/configure the signal; otherwise, the
"N/A" signifies that the user cannot change the state of the signal.
Table 4.2-15 PLC connection points (Input point for PLC#1 user a configurable condition)
Signal Number
511001 810201EE57
511001 810202EE57
Table 4.2-16 PLC connection points (Input point for PLC#2 operate command Closing)
Signal Number
511001 820201EE5E
511001 820202EE5E
Table 4.2-17 PLC connection points (Input point for PLC#3 operate command Closing)
Signal Number
511001 800201EE56
511001 800202EE56
Table 4.2-18 PLC connection points (Input point for operate condition logic)
Signal Number
511001 800201EE65
user may experience an operational failure if the default settings are
used.
Signal Name
Description
DPSY01IN_TMP_35
DPSY01 user configurable condition(PLC#1)
DPSY02IN_TMP_35
DPSY02 user configurable condition(PLC#1)
Signal Name
Description
DPSY01IN_TMP_44
DPSY01 user configurable condition(PLC#2)
DPSY02IN_TMP_44
DPSY02 user configurable condition(PLC#2)
Signal Name
Description
DPSY01IN_TMP_34
DPSY01 user configurable condition(PLC#3)
DPSY02IN_TMP_34
DPSY02 user configurable condition(PLC#3)
Signal Name
Description
DPSY01IN_TMP_40
DPSY01 user additional condition(PLC#1)
- 582 -
6F2S1915 (0.46)
. See PLC#3 of Table 4.2-8.
M/O
O
O
M/O
O
O
M/O
O
O
M/O
O
GRZ200 (Soft 031 & 032)
.