Download Print this page

Toshiba GR200 Series Instruction Manual page 718

Hide thumbs Also See for GR200 Series:

Advertisement

Synchk_Ry (Function ID: 561001)
Setting items
Synchronizing
check relay 1
SyncRy1-VR
SyncRy1-VI
OVR1
UVR1
OVI1
UVI1
SyncRy1-Angle
SyncRy1-dV
SyncRy1-df
SyncRy1-TCB
Synchronizing
check relay 2
SyncRy2-VR
SyncRy2-VI
OVR2
UVR2
OVI2
UVI2
SyncRy2-Angle
SyncRy2-dV
SyncRy2-df
SyncRy2-TCB
Range
Unit
V-L1 / V-L2 / V-
L3 / V-L12 / V-
L23 / V-L31 /
V2-L1 / V2-L2 /
- Running Voltage
V2-L3 / V2-L12 /
V2-L23 / V2-L31
/ V3 / V4
V-L1 / V-L2 / V-
L3 / V-L12 / V-
L23 / V-L31 /
V2-L1 / V2-L2 /
- Incoming Voltage
V2-L3 / V2-L12 /
V2-L23 / V2-L31
/ V3 / V4
10 - 150
V Voltage for the checking Live-Running Voltage
Voltage
10 - 150
V
Voltage
Voltage
10 - 150
V
Voltage
Voltage for the checking Dead-Incoming
10 - 150
V
Voltage
0 - 75
deg Difference angle for the checking SyncRy1
0 - 150
V Difference voltage for the checking SyncRy1
0.01 - 2.00
Hz Difference frequency for the checking SyncRy1
10 - 500
ms CB Operate timer for SyncRy1
V-L1 / V-L2 / V-
L3 / V-L12 / V-
L23 / V-L31 /
V2-L1 / V2-L2 /
- Running Voltage
V2-L3 / V2-L12 /
V2-L23 / V2-L31
/ V3 / V4
V-L1 / V-L2 / V-
L3 / V-L12 / V-
L23 / V-L31 /
V2-L1 / V2-L2 /
- Incoming Voltage
V2-L3 / V2-L12 /
V2-L23 / V2-L31
/ V3 / V4
10 - 150
V Voltage for the checking Live-Running Voltage
Voltage
10 - 150
V
Voltage
Voltage
10 - 150
V
Voltage
Voltage for the checking Dead-Incoming
10 - 150
V
Voltage
0 - 75
deg Difference angle for the checking SyncRy2
0 - 150
V Difference voltage for the checking SyncRy2
0.01 - 2.00
Hz Difference frequency for the checking SyncRy2
10 - 500
ms CB Operate timer for SyncRy2
- 697 -
Contents
for
the
checking
Dead-Running
for
the
checking
Live-Incoming
for
the
checking
Dead-Running
for
the
checking
Live-Incoming
6F2S1915 (0.46)
Default
Note
V3
V-L1
51
13
51
13
30
150
1.00
100
V4
V-L1
51
13
51
13
30
150
1.00
100
GRZ200 (Soft 031 & 032)

Advertisement

loading

This manual is also suitable for:

Grz200