Miscellaneous functions
2.14.4
OVG operation blocked by the occurrence of VT failure
(i)
Blocking the OVG function may be required when a failure in the voltage transformer occurs.
The user shall set Block for scheme switch [OVG1-VTFBlk]. Non (as a default) is set for scheme
switch [OVG1-VTFBlk] in order that the OVG function is not blocked by the failure.
Switch of OVG trip command
(ii)
The OVG function issues a trip command for the TRC† when Trip is set for scheme switch
[OVG1-UseFor] as the normal trip operation. However, when an alarm signal in place of the
trip command is required, the user can set Alarm for the scheme switch [OVG1-UseFor].
†Note: For more information of the trip circuit, see Chapter
circuit
Execution of OVG function
(iii)
Set On for scheme switch [OVG1-EN]. Otherwise, set Off for the scheme switch [OVG1-EN] if
the OVG1 element is not required to operate.
Scheme logic
2.14.5
Figure 2.14-4 shows the OVG function logic. Signal connection points "OVG*_BLOCK" are
provided for the block of the operation of the OV elements. For testing, the OVG1-PU element
is provided; it generates a pick-up signal when the entering voltage is excesses of the threshold
anytime. Thereby, in the IDMT characteristic, using both monitoring points "8000011C23" and
"8000011C27" can facilitate to measure the pickup time after the excess.
.
- 257 -
6F2S1915 (0.46)
Relay application: Trip
GRZ200 (Soft 031 & 032)