Instantaneous and blocking TRIP commands
The Z*G element is able to operate in an instantaneous mode by using the scheme switch
[Z1CNT_INSTOP]. Furthermore, the scheme switch [LEG_EN] can block this element. The
scheme switch [Z*G-PSBBLK] is selected for blocking the tripping when a power swing occurs
in the system. A residual overcurrent element (EFL) is provided as a common function. A value
can be set using the setting [EFL].
From Z1G to Z5G logics
Z1G-TRIP-A
Z1G-TRIP-B
Z1G-TRIP-C
Z1XG-TRIP-A
Z1XG-TRIP-B
Z1XG-TRIP-C
Z2G-TRIP-A
Z2G-TRIP-B
Z2G-TRIP-C
Z3G-TRIP-A
Z3G-TRIP-B
Z3G-TRIP-C
Z4G-TRIP-A
Z4G-TRIP-B
Z4G-TRIP-C
Z5G-TRIP-A
Z5G-TRIP-B
Z5G-TRIP-C
Z1G-OPT-A
Z1G-OPT-B
Z1G-OPT-C
Z1XG-OPT-A
Z1XG-OPT-B
Z1XG-OPT-C
Z2G-OPT-A
Z2G-OPT-B
Z2G-OPT-C
Z3G-OPT-A
Z3G-OPT-B
Z3G-OPT-C
Z4G-OPT-A
Z4G-OPT-B
Z4G-OPT-C
Z5G-OPT-A
Z5G-OPT-B
Z5G-OPT-C
Z1G-ARC-BLOCK
Z1XG-ARC-BLOCK
Z2G-ARC-BLOCK
Z3G-ARC-BLOCK
Z4G-ARC-BLOCK
Z5G-ARC-BLOCK
Figure 2.1-51 ZG grouping logic for TRC/Recording functions
≥1
≥1
≥1
≥1
≥1
≥1
≥1
- 79 -
6F2S1915 (0.46)
To TRC
To DISCAR
8000001B20
ZG-TRIP-A
8100001B21
ZG-TRIP-B
8200001B22
ZG-TRIP-C
8800001B70
ZG-OPT-AR
8900001B7E
ZG-OPT-BR
8A00001B7F
ZG-OPT-CR
8500001B7C
ZG-ARC-BLOCK
GRZ200 (Soft 031 & 032)