O2 Content Air - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
Params & Display>
O2Contr/Alarm>
Type of Fuel (S)
Gas/Oil Settings
V_LNmin (Gas) (S)
V_Lnmin (Oil) (S)
V_afNmin (Gas) (S)
Params & Display>
V_afNmin (Oil) (S)
O2Contr/Alarm>
Gas/Oil Settings>
V_atrNmin (Gas) (S)
Fuel user-def
V_atrNmin (Oil) (S)
B/1000 (S)
Params & Display>
O2Contr/Alarm>
O2 Content Air (O)
Gas/Oil Settings
OptgMode COx Gas (S)
Params & Display>
OptgMode COx Oil (S)
O2Contr/Alarm>
COx
Time COx Alarm (S)
SCC Inc.
Default
Range
user def
naturalGasH
natural
naturalGasL
GasH
propane
butane
user def
oil EL
oil EL
Oil H
9.9
0-40
11.2
10.93
0-40
12.02
8.89
0-40
10.53
A2 (S)
0.65
0.40-0.80
9
1-20
20.9%
0-30%
deactivated
deact
COx Control
deact
COx Limiter
0s
0-600s
This enables the user to pick what type of fuel will be burnt with the O2 Control / O2 Alarm
when firing gas. Options : User defined (see below), naturalgasH (at or above 960 Btu/SCF),
naturalgasL (below 960 Btu/SCF), propane, butane.
This enables the user to pick what type of fuel will be burnt with the O2 Control / O2 Alarm
when firing oil. Options : User defined (see below), Oil EL (Light oil #2), Oil H (Heavy oil #6)
For user-defined fuels, this represents the volumetric fuel / air ratio needed for
stoichiometric combustion of the fuel.
For user defined fuels, this represents the quantity of flue gas generated (wet basis) when
either one cubic meter (for gases) or one kg (for oil) of fuel is combusted at stoichiometric
conditions.
For user defined fuels, this represents the quantity of flue gas generated (dry basis) when
either one cubic meter (for gases) or one kg (for oil) of fuel is combusted at stoichiometric
conditions.
For user defined fuels, these values are adjustable constants for calculating the combustion
efficiency when firing gas or oil.
Defines the O2 content of the combustion air. The LMV52 must see this value +/- 2% during
prepurge. This value can be adjusted if O2 enriched air is used.
Future functionality. Does nothing at this time.
Page 27
HOME
P - LIST
Description
Technical Instructions
LV5-1000
LMV
x x
x x
x x
x x
x x
x x
x x
x x
x
x
x