Siemens LMV5 Series Technical Instructions page 248

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diag.
Device
Display
Code
Code
Any #
01
Oil
Fault Feedback
83
Actuator
Oil Actuator
02
03
Any #
01
Aux 1
Fault Feedback
84
Actuator
Aux Actuator 1
02
03
Any #
01
Aux 2
Fault Feedback
85
Actuator
Aux Actuator 2
02
03
Any #
Fault Feedback
01
86
LMV5
Load Controller
02
03
Any #
01
Fault Feedback
87
AZL5
AZL5
02
03
Any #
All
Fault Feedback
01
Actuator
Actuator
Fault Feedback
02
LMV5
Load Controller
88
Fault Feedback
03
AZL5
AZL
VSD
Fault Feedback
04
module
VSD Module
Fault Feedback
05
O2 Mod.
O2 Module
Section 7
Meaning for the LMV5x System
Fault with Connected Actuators
Basic unit has detected wrong state of the oil actuator
CRC error
Key error main loop counter
No feedback for max. number
Basic unit has detected wrong state of the auxiliary 1 actuator
CRC error
Key error main loop counter
No feedback for max. number
Basic unit has detected wrong state of the auxiliary 2 actuator
CRC error
Key error main loop counter
No feedback for max. number
Fault with Base Unit (LMV5) or AZL5
Basic unit has detected wrong state of the internal load
controller
CRC error
Key error main loop counter
No feedback for max. number
Basic unit has detected wrong state of the AZL
CRC error
Key error main loop counter
No feedback for max. number
Plausibility fault NMT
Undefined fault class of actuator
Undefined fault class of load controller
Undefined fault class of AZL5
Undefined fault class of VSD module
Undefined fault class of O2 module
Page 40
HOME
Corrective Action
1) This fault occurs when an un-addressed actuator is
connected to the CANBus. Addressing the actuator
should eliminate the fault.
2) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
at the LMV5x...
3) Check each CANBus connector to ensure proper
termination (no conductors exposed on the back of the
plug)
4) If fault occurs sporadically: Reduce electrical noise.
5) If fault occurs constantly: Replace actuator according
to diagnostic code.
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
1) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
at the LMV5
2) Check each CANBus connector to ensure proper
termination (no conductors exposed on the back of the
plug)
3) If fault occurs sporadically: Reduce electrical noise.
4) If fault occurs constantly: Replace AZL5...
If fault occurs sporadically, reduce electrical noise.
If fault occurs constantly, replace the defective unit (see
diagnostic code) or the LMV5.
Note: The internal load controller and VSD module are
part of the LMV5.