Open Safety Loop - Error Code 21 - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
The safety loop is meant only for safety limits such as an auxiliary low water cutout or a high 
limit.  The safety loop must be complete, and cannot be reconfigured.  The wiring of the safety 
loop is shown below: 
 
 
If an error code 21 is encountered, check the following: 
 
1. The burner flange switch wired between terminals X3‐03.1 and X3‐03.2.  There should be 
120 VAC on terminal X3‐03.1 at all times.  If a burner flange switch is not present, a jumper 
must be placed between terminals X3‐03.1 and X3‐03.2. 
 
2. Operating switches in the safety loop.  Operating (cycling) switches should not be wired 
into the safety loop.  If a cycling switch is placed in this loop and it cycles off, the LMV5 will 
lockout.  The cycling switch should be relocated in series with the burner on / off switch 
wired to X5‐03.1: 
 
 If the LMV5 is in any external load controller mode (ExtLC...), this is used to cycle the 
burner on and off.  
 If the LMV5 is in any internal load controller mode (IntLC...), then a cycling switch 
may not be necessary, since this is done automatically in the LMV5 using parameters 
SD_ModOn and SD_ModOff. 
 
3. The safety loop between terminals X3‐04.1 and X3‐04.2.  There should be 120 VAC on 
terminal X3‐04.1 at all times.  If there is not, then one or more of the devices wired into the 
safety loop are open.  Check each device wired into the safety loop to find which one is 
open. 
 
 
 
 
 
Section 7 
 
 
Open Safety Loop – Error Code 21 
Page 10 
HOME
LMV Series 
 
SCC Inc. 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents