LMV Series
Technical Instructions
Document No. LV5-1000
9-4: AZL5 Software Updates
The AZL5 software package is frequently updated with new parameters and features. The
software of any AZL5 can be updated using the ACS450 software. If the AZL5 ever states that
there is a "Version Conflict" when it is connected to the LMV5, the AZL5 software needs to be
updated via the ACS450 software.
The current software version of the AZL5 can be checked via the following menu path on the
AZL5:
Params & Display > Access w-out PW > AZL > SW Version
At the time of publication, the latest software version is 5.10, which will display as "0510" on
the AZL5.
The following steps outline the procedure for updating the software version of the AZL5.
1. Ensure that ACS450 is installed on the computer being used to update the AZL5 software.
See Section 9-2 if necessary.
Note: Prior to attempting an AZL5 software update, deactivate the Modbus port (RJ45) on the
bottom of the AZL5 if it is being used. The port can be deactivated under:
Operation > OptgModeSelect > GatewayBASoff
2. Locate the correct .bin file. The ACS450 will prompt for the file later in this procedure. The
.bin file that is necessary for the update is shown below. If the .bin file cannot be located, it can
be acquired from the SCC Combustion CD or by emailing techsupport@scccombustion.com.
• AZL52.00_V0510.BIN
3. Connect the PC to the AZL5 using the necessary cables. The requirements of this
connection are outlined in Section 9-3.
SCC Inc.
Page 5