Configuring (Parameterization Of) An Lmv5 With A Default Parameter Set - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
Configuring (Parameterization of) an LMV5 with a Default Parameter Set 
 
The  procedure  below  assumes  an  LMV5  with  a  default  parameter  set.    If  the  LMV5  is  mounted  to  a 
burner  /  boiler,  the  OEM(s)  may  have  already  changed  the  parameters  from  the  default  setting  and 
parameterized the LMV5 for the application. 
 
Section  3  (Parameters)  gives  a  detailed  explanation  of  all  of  the  parameters  in  the  LMV5,  as  well  as 
highlights which parameters must be set (marked with a double asterisk **) and which parameters are 
frequently used (shaded). 
 
This procedure gives a general guideline of what parameters need to be set to get an LMV5 running on a 
typical  burner/  boiler.  Every  burner  is  different,  so  it  is  likely  that  every  burner  will  need  a  somewhat 
unique parameter set to run correctly. 
 
When an LMV5 with a default parameter set is powered up and wired correctly, it will go into alarm and 
state that "no fuel train is defined".  During the parameterization, the alarm does not need to be reset.  
Moreover,  the  alarm  will  come  back  immediately  until  at  least  a  few  key  parameters  are  set.  The 
recommendation  is  to  silence  the  alarm  horn,  and  leave  the  LMV5  in  a  state  of  alarm  until  the  key 
parameters are set. 
 
1. Log  in  at  the  OEM  password  level.    From  the  factory,  the  OEM  password  for  the  LMV5  is 
"START". 
 
2. Set the Burner ID.  This can be found in the main menu under Updating. The OEM password will 
be  required  when  the  Updating  menu  is  entered.  The  Burner  ID  is  a  unique  number  which 
matches  the  burner  to  the  parameter  set  in  the  LMV5.    Typically,  the  serial  number  of  the 
burner is used as the Burner ID. 
 
3. Configure the load controller sensor (except LMV51.0...) using the following menu path:  
 
Params & Display > LoadController > Configuration 
 
The  default  configuration  is  for  a  hot  water  boiler  (temperature  control)  with  a  PT100  RTD 
temperature sensor. For a steam boiler (pressure control), set the following parameters to the 
following settings: 
 
Sensor Select = PressSensor 
Ext Inp X61 U/I = 0..10V or 4..20mA (sensor dependent) 
MRangePressSens = High range of pressure sensor 
 
4. Set the fuel train(s). If only gas is to be fired, only a gas fuel train must be selected.  If only oil is 
to be fired, only an oil fuel train must be selected.  For dual fuel burners, both a gas and oil fuel 
train must be selected.  Fuel trains can be set using the following menu path: 
 
Params & Display > BurnerControl > Configuration > ConfigGeneral 
 
See  the  following  pages  for  fuel  train  information.  "Pilot  Gp2"  is  typical  for  gas  piloted  gas 
burners and "LO w Gasp" is typical for gas piloted oil burners. 
 
Section 4 
 
Page 6 
HOME
LMV Series 
SCC Inc. 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents