Siemens LMV5 Series Technical Instructions page 131

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series 
 
 
NOTE:  Make sure that the direction of rotation is set correctly for all actuators at this time, 
including the oil actuator.  If the direction of rotation must be changed later, the fuel‐air ratio 
control curves must be deleted. 
 
8. At  this  point,  the  LMV5  alarm  can  be  reset,  provided  that  there  is  not  a  call  for  heat  present 
(burner switch is off / X5‐03.1 is not energized).  Older LMV5 units also require the safety loop to 
be  closed  before  the  alarm  can  be  reset.  The  reset  can  be  accomplished  via  a  remote  reset 
button (if wired) or via the menu path: 
 
OperationalStat > Status/Reset > Press "ESC" then "ENTER" to reset 
 
9. Set actuator home (standby) positions if necessary. Defaults are 0 degrees and 0% VSD. For dual 
fuel burners this will need to be done for both fuels. The menu path is:  
 
Params  &  Display  >  RatioControl  >  GasSettings  or  OilSettings  >  SpecialPositions  > 
HomePos 
 
10. Couple actuators to the valves / dampers. Actuators must not torque against mechanical stops 
on the valve / damper when at home position. Adjust home positions if necessary. 
 
NOTE:  Actuator shaft couplings must compensate for both angular and parallel shaft 
misalignment due to the mounting bracket. Solid (rigid) shaft couplings are not acceptable in 
most applications, especially when formed or welded mounting brackets are used.  Couplings 
should have little to no backlash, and are a safety relevant part of a linkage‐less system.  
 
NOTE:  Make absolutely certain that when the actuators are at or near 0 degrees (as indicated 
on the AZL display) that the valve / damper the actuator is coupled to is in the CLOSED 
(minimum flow) position. An exception to this is some back‐flow type oil burners, where a 
wide open oil valve will result in minimal flow thru the oil nozzle. 
 
11. With the burner off, stroke each valve / damper through its intended range of motion using the 
SQM... actuator that is now coupled to the valve / damper. The menu path to do this is: 
 
Params & Display > RatioControl > GasSettings or OilSettings > CurveParams 
(For oil, also go into Curve Settings) 
 
In  the  Curve  Parameters  screen,  all  of  the  activated  actuators  for  the  selected  fuel  can  be 
stroked through their intended range of motion. An arrow (>) indicates the actuator is driving to 
the set position and a colon (:) indicates that the actuator is at the set position.  Verify that no 
binding  will  occur  through  the  intended  range  of  motion.    Also  note  valves  /  dampers  where 
wide open is less than 90 degrees.  
 
12. Set special positions for all activated actuators.  This will define where the actuators / VSD go for 
ignition,  pre‐purge,  and  post‐purge.    For  dual  fuel  burners  this  will  need  to  be  done  for  both 
fuels.  Special positions can be set using the following menu path: 
 
 
Params & Display > RatioControl > GasSettings or OilSettings > SpecialPositions 
 
SCC Inc. 
 
 
Page 13 
HOME
Technical Instructions 
Document No. LV5‐1000 
Section 4 