O 2 Trim Configuration (Parameterization) Before Commissioning - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series 
 
 
The O
 Ratio Control Curve reflects the %O
2
The O
 Control Curve is the target for the O
2
transitioned from the O
 Ratio Control Curve to the O
2
Value, the Lambda Factor will be learned and recorded at that specific point.  A larger gap between the 
O
 Ratio Control Curve and the O
2
Lambda Factor of the burner, and thus yield the best pre‐control when the burner is modulating.  A gap 
of 1% O
 or more is ideal, and it is typically achievable on nozzle mixing burners with no or low 
2
percentages of FGR.  A 1% gap is typically not achievable on premix mesh burners or on nozzle mixing 
burners that use a high percentage of FGR.  This gap also sets the available quantity of "lean" trim for an 
LMV52.240, and that is why the minimum recommended gap for an LMV52.240 is 1%.  The LMV52.440 
uses a different O
 trim algorithm for premix, mesh and high percentage FGR burners and can deal with 
2
a minimum gap of 0.5%. 
 
  
O
 Trim Configuration (Parameterization) Before Commissioning 
2
 
The procedure below assumes an LMV52 with default parameters for the O2 Contr/Alarm menu and the 
O2 Module menu.  If the LMV52 is mounted to a burner / boiler, the burner / boiler OEM may have 
already changed the parameters from the default setting and parameterized the LMV52 for the 
application.  This procedure also assumes that all O
and that the O
 trim will be commissioned on natural gas. 
2
 
Section 3 gives a detailed explanation of all of the parameters in the LMV52 as well as highlights which 
parameters must be set (marked with a double asterisk **) and which parameters are frequently used 
(shaded). 
 
This procedure gives a general guideline of what parameters need to be set on both a traditional nozzle 
mixing burner with little to no FGR, and also for low and ultra‐low NOx burners that are pre‐mix mesh 
type  or  high  percentage  FGR.    Every  burner  is  different,  so  it  is  likely  that  every  burner  will  need  a 
somewhat unique parameter set to run correctly. 
 
1. Log in at the OEM password level.  From the factory, the OEM password for the LMV5 is "START". 
 
2. If not done so already, activate the O
 
Params & Display > O2 Module > Configuration > O2 Sensor = QGO20 
 
3. If being used, configure the appropriate temperature sensors for blower inlet air temperature and 
stack temperature.  This is done through the following menu path: 
 
Params & Display > O2 Module > Configuration > SupAirTempSens 
Params & Display > O2 Module > Configuration > FlueGasTempSens 
 
Parameter SupAirTempSens activates and configures the blower inlet air temperature sensor.  
Parameter FlueGasTempSens activates and configures the stack temperature sensor.  Options are 
Ni1000 or Pt1000 2‐wire sensors for both inputs. 
 
SCC Inc. 
 
 
 that resulted from setting the Fuel‐Air Ratio Control Curve. 
2
 trim system when it is activated.  When the burner is 
2
 Control Curve by increasing the Standardized 
2
 Control Curve will give the LMV52 the best opportunity to learn the 
2
 trim components are installed and wired correctly, 
2
 sensor using the following menu path: 
2
Page 7 
HOME
Technical Instructions 
Document No. LV5‐1000 
Section 6 
 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents