Special Features And Settings - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
Special Features and Settings 
 
The  LMV5  has  special  features  and  settings  that  are  very  useful  in  some  situations.  Some  of  these 
features are detailed below. 
 
Alarm act/deact 
An internal alarm silence.  Alarm silence will reset when the LMV5 alarm is reset. 
 
MinTmeStartRel 
Permits the LMV5 to hold in phase 21 for a specified period of time with the start 
signal terminal energized.  This can be used as a delay to let stack and/or fresh air 
dampers open. 
 
PressReacTme  
Allows  the  LMV5  to  disregard  the  high  and  low  gas  /  oil  pressure  switches  for  a 
settable  time  period  after  the  main  gas  /  oil  valves  open.    This  is  used  with 
automatic reset pressure switches so that pressure spikes due to the main valves 
opening  will  be  ignored.    This  also  allows  for  a  reduced  delta  between  switch 
setpoints and normal operating  pressures.  This time can also be reduced to 0.2 
seconds, deactivating the feature.  Not used with manual reset switches. 
 
NormDirectStart 
Permits  the  LMV5  to  go  from  post‐purge  directly  into  pre‐purge  without  turning 
the blower off.  The blower air pressure switch must be checked by using a 3‐way 
solenoid valve.  The solenoid valve is configured under parameter StartSignal. 
 
ForcedIntermit 
Shuts the burner down once every 24 hours to cycle and check flame scanner, air 
pressure switch, POC, and other safety devices. 
 
DriveLowFire 
Starts driving to low fire (StartPointOp) immediately after main fuel valves open.  
Enables less air to be put on the pilot for ignition, and enables a fuel rich light off 
without creating excessive CO.  Also called "Golden Start" functionality. 
 
StartReleaseGas 
Configures terminal X7‐03.2 as a start release for gas, CPI gas, CPI oil, or CPI gas + 
oil.  Gas and oil POCs can be wired here, freeing up terminal X9‐03.2 for gas valve 
proving.  CPI stands for Closed Position Indication, which is essentially the same as 
Proof of Closure (POC). 
 
Config_PS‐VP/CPI 
Configures terminal X9‐03.2 for PS‐VP (Pressure Switch ‐ Valve Proving), CPI gas, 
CPI  oil,  or  CPI  gas  +  oil.    CPI  stands  for  Closed  Position  Indication,  which  is 
essentially the same as Proof of Closure (POC). 
 
Config X5‐03 
Terminal  X5‐03.3  can  be  configured  to  hold  the  LMV5  in  phase  36  (ignition 
position).  Terminal X5‐03.2 can be configured to disable O
 
HeavyOilDirStart 
Terminal X6‐01.3 can be used as an input for an external flame relay. 
 
ReacTmeLossFlame  Adjustable flame failure response time (FFRT).  
 
 
Section 4 
 
Page 30 