Flame Failure - Error Code 25 Or 26 - Siemens LMV5 Series Technical Instructions

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
If either an error code 25 or error code 26 is encountered, a flame failure has occurred.  An 
error code 25 means that a flame failure occurred during pilot, while an error code 26 means 
that a flame failure occurred during operation. To remedy either fault, check the following: 
 
1. Increase the flame failure response time through the following menu path: 
 
Params & Display > BurnerControl > Configuration > ConfigFlameDet > ReacTmeLossFlame 
The LMV5 has a base flame failure response time of 0.8 seconds.  The setting of parameter 
ReacTmeLossFlame adds an additional 0.2 – 3.2 seconds for a maximum of a 4 second 
flame failure response time (FFRT). 
 
2. Use a flame source to check if the flame scanner is defective.  The flame signal can be 
viewed using the following menu path: 
 
Params & Display > BurnerControl > Configuration > ConfigFlameDet > FlameSignal 
 
Parameter FlameSig QRI_B can be used to view the flame signal when using an infrared 
scanner (QRI2...) or an ultraviolet scanner (QRA7...).  Parameter FlameSig ION can be used 
to view the flame signal when using a flame rod.  A flame failure occurs below a 20% flame 
signal.  If the flame signal reads 0% when using a flame source, check the wiring of the 
scanner.  See Section 2 for wiring assistance.  If the wiring is correct, replace the defective 
scanner. 
 
3. If an error code 25 occurred, check the wiring of the ignition transformer and pilot valve.  
Also, check to make sure any manual shutoff valves are open on the pilot line. 
 
4. If an error code 25 occurred, check the position of the air damper during ignition.  This can 
be viewed using the following menu path: 
 
Params & Display > RatioControl > Gas Settings > SpecialPositions > IgnitionPos > 
IgnitionPosAir 
 
Decrease this position if the pilot flame is being blown out. 
 
5. If an error code 26 occurred, there could be flame signal decay due to glowing refractory 
inside the boiler.  If this is the case, replace the QRI2... infrared scanner with a QRA7... 
ultraviolet scanner. 
 
 
Section 7 
 
Flame Failure – Error Code 25 or 26 
 
 
Page 8 