Siemens LMV5 Series Technical Instructions page 144

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Technical Instructions 
Document No. LV5‐1000 
 
d. Temperature / Time‐based Stepping Start Combination 
This method combines methods b and c and if set correctly, is the fastest way to safely 
warm  the  boiler.    The  settings  are  similar  to  method  b,  but  now  parameter 
MaxTmeMod is set to have an effect (10 minutes for example).  When this is done, the 
maximum  time  that  a  step‐up  in  load  will  take  is  10  minutes,  regardless  of  the 
temperature  change.    If  the  temperature  change  defined  by  StageSetp_Mod  happens 
before the 10 minutes elapses, then the temperature change will trigger the step‐up in 
load.  
 
When  this  mode  is  used,  time  usually  triggers  the  load  steps  at  the  start  of  boiler 
warming  and  temperature  change  usually  triggers  the  load  steps  closer  to  the 
ThresholdOff  temperature.  This  is  due  to  the  more  rapid  rise  in  boiler  temperature  at 
higher firing rates. 
 
After parameters are set for one of the methods above, set parameter ColdStartOn to activated. 
5.
The  next  time  the  burner  is  started  and  the  water  temperature  is  below  the  ThresholdOn 
temperature, cold start should engage. 
 
Below are typical settings for each of the four ways cold start can be set up. 
 
Example:  Steam Boiler with an Additional Temperature Sensor 
Parameter 
ColdStartOn 
ThresholdOn 
StageLoad 
StageSetp_Mod 
StageSetp_Stage 
MaxTmeMod 
MaxTmeStage 
ThresholdOff 
AdditionalSens 
Temp. ColdStart 
Setp AddSensor 
Release Stages 
 
 
The following page shows an example of a time‐based stepping start. 
 
 
 
 
 
 
 
 
Section 4 
Low Fire Hold 
Temp‐based 
0% 
N/A 
N/A 
63 min 
Figure 4‐8:  Typical Cold Start Parameter Settings 
Page 26 
HOME
 
Time‐based 
Activated 
50% (= 150°F) 
5% 
5% 
5% 
100% 
Staged Operation Only 
5 min 
Staged Operation Only 
80% (= 240°F) 
Pt1000 
Read Only 
300°F 
Staged Operation Only 
LMV Series 
Temp/time‐based 
5% 
10% 
10 min 
SCC Inc. 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents