At the end of the calculations, p0340 is automatically set to 0.
If the STARTER commissioning software writes a 3 into p0340 when "downloading to target device", then this
corresponds to a "complete calculation of the motor/control parameters without equivalent circuit diagram data". The
same calculations are carried out as for p0340 = 1, however, without the equivalent circuit diagram parameters of the
motor (p0340 = 2), the motor moment of inertia (p0341) and the motor mass (p0344).
For third-party linear synchronous motors (p0300 = 4) equivalent circuit diagram data are not calculated (p0340 = 2).
p0341[0...n]
Motor moment of inertia / Mot M_mom of inert
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL
Min
0.000000 [kgm²]
Description:
Sets the motor moment of inertia (without load).
Dependency:
IEC drives (p0100 = 0): unit kg m^2
NEMA drives (p0100 = 1): unit lb ft^2
The parameter value is included, together with p0342, in the rated starting time of the motor.
Refer to: p0342, r0345
Notice:
When selecting a catalog motor (p0301), this parameter is automatically pre-assigned and is write protected.
Information in p0300 should be carefully observed when removing write protection.
Note:
SERVO:
p0341 * p0342 + p1498 influence the speed/torque pre-control in encoderless operation.
VECTOR:
The product of p0341 * p0342 is used when the speed controller (p0340 = 4) is calculated automatically.
p0342[0...n]
Ratio between the total and motor moment of inertia / Mot MomInert Ratio
VECTOR_G
Can be changed: C2(3), U, T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: REL
Min
1.000
Description:
Sets the ratio between the total moment of inertia (load + motor) and the intrinsic motor moment of inertia (no load).
Dependency:
This means that together with p0341, the rated starting (accelerating time) of the motor is calculated for a vector
drive.
Refer to: p0341, r0345, p1498
Note:
SERVO:
p0341 * p0342 + p1498 influence the speed/torque pre-control in encoderless operation.
VECTOR:
The product of p0341 * p0342 is used when the speed controller (p0340 = 4) is calculated automatically.
p0343[0...n]
Rated motor current identified / Mot I_rated ident
VECTOR_G
Can be changed: C2(3), T
Data type: FloatingPoint32
P-Group: Motor
Not for motor type: PMSM, SESM, REL,
RESM
Min
0.00 [Arms]
Description:
Displays the identified rated motor current.
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
Calculated: CALC_MOD_ALL
Dyn. index: MDS, p0130
Unit group: 25_1
Scaling: -
Max
100000.000000 [kgm²]
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
10000.000
Calculated: -
Dyn. index: MDS, p0130
Unit group: -
Scaling: -
Max
10000.00 [Arms]
2 Parameters
2.2 List of parameters
Access level: 3
Func. diagram: 5042, 5210,
6020, 6030, 6031
Unit selection: p0100
Expert list: 1
Factory setting
0.000000 [kgm²]
Access level: 3
Func. diagram: 5042, 5210,
6020, 6030, 6031
Unit selection: -
Expert list: 1
Factory setting
1.000
Access level: 4
Func. diagram: -
Unit selection: -
Expert list: 1
Factory setting
0.00 [Arms]
143