2 Parameters
2.2 List of parameters
Dependency:
Refer to: p3665
Refer to: F34207, A34211
Note:
If value r3666 exceeds threshold value p3667 or p3668, then alarm A34211 or fault F34207 is output.
For sensor type PTC (p3665 = 1), the following applies:
- below the nominal response temperature, r3666 = -50°C.
- above the nominal response temperature, r3666 = 250 °C.
p3667[0...n]
VSM overtemperature alarm threshold / VSM T A thresh
VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-100.00 [°C]
Description:
Sets the alarm threshold for the temperature sensor on the Voltage Sensing Module (VSM).
Prerequisite:
A KTY/PT1000 temperature sensor is connected, and correspondingly p3665 is set = 2, 6.
Dependency:
Refer to: p3665
Refer to: A34211
Note:
For sensor type KTY (p3665 = 2), values 181 ... 300 °C result in fault F06255.
The monitoring is deactivated for p3667 = 301.
p3668[0...n]
VSM overtemperature shutdown threshold / VSM T F_thresh
VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
-100.00 [°C]
Description:
Sets the shutdown threshold for the temperature sensor of the VSM.
Prerequisite:
A KTY/PT1000 temperature sensor is connected, and correspondingly p3665 is set = 2, 6.
Dependency:
Refer to: p3665, p3667
Refer to: F35207
Note:
For sensor type KTY (p3665 = 2), values 181 ... 300 °C result in fault F06255.
The monitoring is deactivated for p3668 = 301.
p3669[0...n]
VSM overtemperature hysteresis / VSM T hyst
VECTOR_G
Can be changed: T
Data type: FloatingPoint32
P-Group: -
Not for motor type: -
Min
1.00 [K]
Description:
Sets the hysteresis for the alarm threshold of the Voltage Sensing Module (VSM).
Dependency:
Refer to: p3667
612
Calculated: -
Dyn. index: p0150
Unit group: 21_1
Scaling: p2006
Max
301.00 [°C]
Calculated: -
Dyn. index: p0150
Unit group: 21_1
Scaling: p2006
Max
301.00 [°C]
Calculated: -
Dyn. index: p0150
Unit group: 21_2
Scaling: p2006
Max
50.00 [K]
List Manual (LH2), 07/2016, A5E03263479A
Access level: 3
Func. diagram: 9886
Unit selection: p0505
Expert list: 1
Factory setting
150.00 [°C]
Access level: 3
Func. diagram: 9886
Unit selection: p0505
Expert list: 1
Factory setting
180.00 [°C]
Access level: 3
Func. diagram: 9886
Unit selection: p0505
Expert list: 1
Factory setting
3.00 [K]
SINAMICS G130/G150