Siemens G130 List Manual page 681

Hide thumbs Also See for G130:
Table of Contents

Advertisement

[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: r4105, p4111, r4112, r4113, p4122
p4121
TM150 filter rated line frequency / TM150 filt f_line
TM150
Can be changed: T
Data type: Integer16
P-Group: -
Not for motor type: -
Min
0
Description:
Sets the rated line frequency for the filter to skip the line frequency for Terminal Module 150 (TM150).
Value:
0:
1:
p4122[0...11]
TM150 smoothing time constant / TM150 T
TM150
Can be changed: T
Data type: Unsigned16
P-Group: -
Not for motor type: -
Min
100 [ms]
Description:
Sets the smoothing time constant for the 1st order lowpass filter of the temperature channels.
The effective smoothing time constant depends on the number of channels that are simultaneously active and is
displayed in r4120.
In order that the value becomes effective, p4122 must be set >= 2 *channel sampling time.
The following applies:
Channel sampling time = active number of channels * 50ms
For lower values, a smoothing of 2 * channel sampling time.
Index:
[0] = Temperature channel 0
[1] = Temperature channel 1
[2] = Temperature channel 2
[3] = Temperature channel 3
[4] = Temperature channel 4
[5] = Temperature channel 5
[6] = Temperature channel 6
[7] = Temperature channel 7
[8] = Temperature channel 8
[9] = Temperature channel 9
[10] = Temperature channel 10
[11] = Temperature channel 11
Dependency:
Refer to: r4120
p4600[0...n]
Motor temperature sensor 1 sensor type / Temp_sens 1 type
VECTOR_G
Can be changed: C2(3), U, T
Data type: Integer16
P-Group: Motor
Not for motor type: -
Min
0
Description:
Sets the sensor type of the first temperature sensor for the motor temperature monitoring.
Value:
0:
10:
11:
12:
20:
30:
SINAMICS G130/G150
List Manual (LH2), 07/2016, A5E03263479A
50 Hz
60 Hz
No sensor
PTC fault
PTC alarm
PTC alarm & timer
KTY84
Bimetallic NC contact fault
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
1
Calculated: -
Dyn. index: -
Unit group: -
Scaling: -
Max
10000 [ms]
Calculated: -
Dyn. index: EDS, p0140
Unit group: -
Scaling: -
Max
60
2 Parameters
2.2 List of parameters
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
0
Access level: 1
Func. diagram: 9626, 9627
Unit selection: -
Expert list: 1
Factory setting
100 [ms]
Access level: 2
Func. diagram: 8016
Unit selection: -
Expert list: 1
Factory setting
0
681

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

SinamicsG150

Table of Contents