Autoreclose Initiation; Autoreclose Shot Output (Arc-Shot); Plc Default Setting - Toshiba GRE110 Instruction Manual

Overcurrent protection relay
Table of Contents

Advertisement

Autoreclose initiation

Programmable binary input ARC-READY(CB& 63condition) is alive and Reclaim time TRDY
has elapsed and Scheme switch [ARCEN] is set to "On," then autoreclose initiation is ready. The
reclaim time is selected by setting [TRDY] to "0.0-600.0s".
ARC INIT(Autoreclose initiation) can consist of the following trips. Whether autoreclose initiation
is active or not is selected by setting [∗∗∗∗-INIT].
- OC1 to OC4 trip
- EF1 to EF4 trip
- SEF1 to SEF4 trip
Setting [∗∗∗∗-INIT] = NA / On / Block
EXT TRIP(External autoreclose initiation) is an autoreclose initiation via programmable binary
inputs. Whether autoreclose initiation is active or not is selected by setting [EXT-INIT].
Setting [EXT-INIT] = NA / On / Block

PLC default setting

302
ARC_READY
CONST 1
[ARCEN]
+
"ON"
EXT_TRIP-A
EXT_TRIP-B
EXT_TRIP-C
EXT_TRIP
ARC_INIT
301
ARC_NO_ACT
ARC_BLOCK

Autoreclose shot output (ARC-SHOT)

The maximum number of autoreclosing shots is selected by setting [ARC-NUM].
Setting [ARC-NUM] = S1/S2/S3/S4/S5
The passage of TD∗ time(Dead timer) is selected for each shot number by setting [TD∗] to
"0.01-300.00s."
The command output pulse(One shot) time is selected by setting [TW] to "0.01-10.00s."
NA: Autoreclose initiation is not active.
On : Autoreclose initiation is active.
Block: Autoreclose is blocked.
TRDY
211
t
0
&
0.0-600.0s
≥1
&
≥1
&
≥1
&
∗∗∗-INIT = "ON"
&
&
ON
&
[EXT-INIT]
BLK
+
∗∗∗-INIT = "BLK"
Figure 2.13.2 Autoreclose Initiation
 57 
≥1
≥1
&
1
≥1
≥1
RS-ARCBLK
210
ARC_BLK_OR
≥1
6 F 2 T 0 1 7 2
ARC initiation
&
TP1
1 cycle