Toshiba GRE110 Instruction Manual page 237

Overcurrent protection relay
Table of Contents

Advertisement

Menu
Name
OC
Protection
UC
Range
OC1
0.10 – 25.00 A
TOC1
0.010 – 1.500
TOC1
0.00 – 300.00 s
TOC1R
0.0 – 300.0 s
TOC1RM
0.010 – 1.500
OC2
0.10 – 25.00 A
TOC2
0.010 – 1.500 s
TOC2
0.00 – 300.00 s
TOC2R
0.0 – 300.0 s
TOC2RM
0.010 – 1.500
OC3
0.10 – 150.00 A
TOC3
0.00 – 300.00 s
OC4
0.10 – 150.00 A
TOC4
0.00 – 300.00 s
OC1-k
0.00 – 300.00
0.00 – 5.00
OC1-α
OC1-C
0.000 – 5.000
OC1-kr
0.00 – 300.00
0.00 – 5.00
OC1-β
OC2-k
0.00 – 300.00
OC2-α
0.00 – 5.00
OC2-C
0.000 – 5.000
OC2-kr
0.00 – 300.00
OC2-β
0.00 – 5.00
UC1
0.10 – 10.0 A
TUC1
0.00 – 300.00 s
UC2
0.10 – 10.00 A
TUC2
0.00 – 300.00 s
Contents
OC1 Threshold
OC1
Time multiplier
(if MOC1≠D)
OC1 Definite
time setting.
(if MOC1=D)
OC1 Definite
time reset delay
(if OC1R=DEF)
OC1 Dependent
time reset delay
(if OC1R=DEP)
OC2 Threshold
OC2 Definite
time setting.
OC2 Definite
time setting.
(if MOC2=D)
OC2 Definite
time reset delay
(if OC2R=DEF)
OC2 Dependent
time reset delay
(if OC2R=DEP)
OC3 Threshold
OC3 Definite
time setting.
OC4 Threshold
OC4 Definite
time setting.
Configurable
IDMT
Curve setting.
(if MOC1=C)
Configurable
IDMT
Curve setting.
(if MOC2=C)
UC1 Threshold
UC1 Definite time
Setting
UC2 Threshold
UC2 Definite time
Setting
 238 
6 F 2 T 0 1 7 2
Default
1.00A
1.000
1.00s
0.0s
1.000
5.00A
1.000s
0.00s
0.0s
1.000
10.00A
0.00s
10.00A
0.00s
0.14
0.02
0.000
2.00
2.00
0.14
0.02
0.000
2.00
2.00
0.40A
0.00s
0.20A
0.00s

Hide quick links: