Binary Output - Toshiba GRE110 Instruction Manual

Overcurrent protection relay
Table of Contents

Advertisement

C N T L C K
O f
f
/
O n
A R C B L K
O f
f
/
O n
A R C N A T
O f
f
/
O n
A R C M C L
O f
f
/
O n
<BI1SNS>
To set the Binary Input 1 Sense, do the following.
• Enter 0(=Normal) or 1(=Inverted) and press the ENTER key.
<BI1SGS>
To set the Binary Input 1 Settings Group Select, do the following.
• Enter 0(=Off) or 1(=1) or 2(=2) or 3(=3) or 4(=4) and press the ENTER key.
<Others>
• Enter 1(=On) to set the function and press the ENTER key. If not setting the function, enter
0(=Off) and press the
• After setting, press the END key to return to the "BI∗" screen.
4.2.6.9

Binary Output

All the binary outputs of the GRE110 except the relay failure signal are user-configurable. It is
possible to assign one signal or up to four ANDing or ORing signals to one output relay. Available
signals are listed in Appendix B.
It is also possible to attach Instantaneous or delayed or latched reset timing to these signals.
Appendix D shows the factory default settings.
CAUTION
When having changed the binary output settings, release the latch state on a digest screen by
pressing the RESET key for more than 3 seconds.
To configure the binary output signals, do the following:
key.
ENTER
 138 
6 F 2 T 0 1 7 2