Bcd Element Characteristic - Toshiba GRE110 Instruction Manual

Overcurrent protection relay
Table of Contents

Advertisement

Positive phase sequence current I
current I
at the fault location in a single-phase series fault are given by:
0F
I
+ I
+ I
=0
1F
2F
0F
− Z
Z
I
I
= 0
2F
2F
0F
0F
− E
− Z
E
= Z
I
1A
1B
1F
1F
where,
E
, E
: power source voltage
1A
1B
Z
: positive sequence impedance
1
Z
: negative sequence impedance
2
Z
: zero sequence impedance
0
From the equations (1), (2) and (3), the following equations are derived.
Z
+ Z
2
0
I
=
1F
Z
Z
+ Z
Z
+ Z
1
2
1
0
−Z
0
I
=
2F
Z
Z
+ Z
Z
+ Z
1
2
1
0
−Z
2
I
=
0F
Z
Z
+ Z
Z
+ Z
1
2
1
0
The magnitude of the fault current depends on the overall system impedance, difference in phase
angle and magnitude between the power source voltages behind both ends.
Broken conductor protection element BCD detects series faults by measuring the ratio of negative
to positive phase sequence currents (I
impedance of the system:
I
|I
|
Z
2F
2F
0
=
=
I
|I
|
Z
+ Z
1F
1F
2
0
The ratio is higher than 0.5 in a system when the zero sequence impedance is larger than the
negative sequence impedance. It will approach 1.0 in a high-impedance earthed or a one-end
earthed system.
The characteristic of BCD element is shown in Figure 2.7.2 to obtain the stable operation.
I
2
0.01
0
0.04
, negative phase sequence current I
1F
(1)
(2)
I
(3)
2F
2F
− E
(E
)
1A
1B
Z
2
0
− E
(E
)
1A
1B
Z
E
2
0
− E
(E
)
1A
1B
Z
2
0
/ I
). This ratio is given with negative and zero sequence
2F
1F
I
1
Figure 2.7.2

BCD Element Characteristic

 41 
and zero phase sequence
2F
| ≥ BCD
|I
|/|I
2
1
setting
&
| ≥ 0.04
|I
1
| ≥ 0.01
|I
2
6 F 2 T 0 1 7 2
BCD

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents