Modbus Address Map Group; Modbus Address Map; Time Synchronization - Toshiba GRE110 Instruction Manual

Overcurrent protection relay
Table of Contents

Advertisement

(2) Modbus address map group

Modbus data model
Address(ID)
Coils
0x0200
(Read/Write)
0x0400
Discrete Input
0x1000
0x1016
(Read Only)
0x1040
0x1080
0x1201
Input Registers
0x2000
(Read Only)
Holding Registers
0x3000
(Read/Write)
0x3200
0x3800
0x3810
0x3E82
0x4000
0x8000
Discrete Inputs
Coils
Input Registers
Holding Registers

(3)Modbus address map

Address
Description
Coils
Remote control (R/W)
0200
Remote control enable flag
0400
Remote control command
0401
Remote interlock command
0402
Remote reset command

Time synchronization

0403
command
Number Data specification
1 Remote control (enable flag)
Remote control (command, interlock), Time
5
synchronization, Clear command (write only)
6 BI
5 Relay fail output, BO
14 LED(Relay status, R/L, CB on/off status)
16 Virtual LED
Signal list (see Appendix B for detail)
Analog data (Ia, Ib, Ic, Ie, Thermal, Ia max etc.,
24
unconverted to engineering units)
2-word long
Fault record (No., Time, Phase, Type), max. 4 records,
29
write protected
Event record (No., Time, ID, Status), 10 out of max. 200
72
records, write protected
4 Current time data (IEC format)
36 Counter data (number of trips, ∑I
2 Password for remote control
- Setting value (see Appendix H for detail)
Undefined after this address
Single bit
Read-Only
Single bit
Read-Write
16-bit word
Read-Only
16-bit word
Read-Write
Supplementary explanation
Write (control) is enabled only 0x0200=1 (on/off)
Write (control) is enabled only 0x0200=1 (on/off)
Write (control) is enabled only 0x0200=1 (on)
Call time synchronization task (on)
 263 
6 F 2 T 0 1 7 2
y
, etc), 2-word long