Relays Expansion Board 4581; Inputs And Outputs Expansion Board 4583 - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
5.2.2.4
5.2.2.5
5.2.2.6
5.2.2.7
5.3
5.4
Short-circuit state
Short-circuit current limit
zone line, which generates a fault condition in EBL128.
Open circuit state
Open circuit current limit
line current consumption, i.e. the end-of-line device is not detected,
which generates a fault condition in EBL128. From this state any
other state can be reached / activated.
Disconnected state
Via menu H5/A2 (Disconnect / Re-connect zone line) the zone line
input can be disconnected
From this state no other state can be reached / activated.
Low voltage state
Zone line low voltage limit (15 V DC) is passed without the high
current state is activated, indicating some H/W fault. This generates a
fault condition in EBL128. From this state any other state can be
reached / activated.

8 relays expansion board 4581

Each board has to be programmed via Win128 regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5, page 23.
The 4581 board has eight programmable relay outputs (Output 0-7).
Connections to "J1:1-16" and "J2" according to drawing 128-31.
Each output has to be programmed via Win128 regarding:
Type, i.e. output for Control, Alarm devices, etc.
Output signal period (steady, pulse, delay, etc.)
Logic, i.e. normally open (NO) or normally closed (NC)
25
contacts
Control expression (one or more trigger conditions)
For more information, see Win128 help and chapter "Programmable
outputs", page 61.
The terminals support a wire size up to 1.13 mm

Inputs and outputs expansion board 4583

Each board has to be programmed via Win128 regarding:
Address (set via the jumpers "JP2-JP4", see Figure 5, page 23.
24
This indicated in EBL128 by the LED "Disablements".
25
Relay contact ratings: Max. 2A @ 30 V DC.
EBL128 Planning Instructions V1.1.x
23
is exceeded, indicating short-circuit on the
23
is passed, indicating no or too low zone
24
, i.e. there is no voltage on the zone line.
2
25
(1.2 mm).