Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
9.5
9.6
9.7
9.8
9.9
The 3361 unit outputs Re0 – Re1
Each 3361 unit has two programmable relay outputs:
Re0 Relay output, NO or NC contacts programmable
Re1 Relay output, NO or NC contacts programmable
Relay contacts: max. 2 A @ 30 V DC / 125 V AC (60W).
Connections and more information, see drawings 128-21 & -26.
The 3364 unit outputs VO0, VO1 & VO2
Each 3364 unit has two programmable, supervised (monitored)
voltage outputs:
VO0 Supervised (monitored) voltage output, 24V DC, max. 1A
VO1 Supervised (monitored) voltage output, 24V DC, max. 1A
VO2 is a voltage output, 24V DC, max. 1A
closing.
Normally high.
Technical Description MEW00529.
24 V DC required from an external power supply unit (e.g. 3366).
Connections, see drawing 128-21 & -28.
The 3377 unit output (siren)
Each 3377 unit has one programmable output:
Output
Siren, with two priority levels and three sound types.
Connections and more information, see drawing 128-21.
The 3378 unit output (sounder)
Each 3378 unit has one programmable output:
Output
Sounder, with two priority levels and three sound types.
Connections and more information, see drawing 128-21.
The 3379 unit output (sounder)
Each 3379 unit has one programmable output:
Output
Sounder, with two priority levels and three sound types.
Connections and more information, see drawing 128-21.
62
Cont. 1 A, during 10 ms 1.4 A.
EBL128 Planning Instructions V1.1.x
62
, intended for fire door
For more information see the
63
59
62