Panasonic EBL128 Planning Instructions page 59

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
1. Default. The input does not work.
2. Key cabinet, where the fire brigade store a key to the building.
Will activate a Key cabinet alarm. See the EBL128 Operating
Instructions for more information.
3. Alert annunciation, see the EBL128 Operating Instructions for
more information.
4. Like 2.
5. Ext. power supply equipment fault output will activate a fault in
EBL128.
The following fault message will be shown:
FAULT: External power supply
6. Ext. fuses (for the ext. power supply equipment) fault output will
activate a fault in EBL128.
The following fault message will be shown:
FAULT: External fuses
7. External clock, timer, key switch, switch, etc. can disable / re-
enable alarm points. The function Alert annunciation can be set
on / off by a time channel. Control outputs can be turned on
(activated) / off (de-activated) by a time channel.
8. A special detector, push button, etc. can activate a fire alarm in
EBL128. Zone no. and Address (+ user definable text).
9. "Activated Fire brigade tx" signal (feed-back) to EBL128 will
light up the LED "Fire brigade tx" on the front. (Normally the
LED will be lit when a corresponding output is activated
Output with trigger condition "Indication Fire Brigade tx
Activated" will be activated.
10. Ext. fault will activate a fault in EBL128. A user definable fault
message ("text") with up to 40 characters will be shown.
11. A feed-back from the equipment activated by the corresponding
interlocking output. Activated input is shown in menu H9/C1.
See also chapter "Interlocking function", page 76.
12. Fault output "Loss of main power source to external power supply
equipment" will activate a fault in EBL128. It will have the same
time delay, as set for the Loss of main power source fault for
EBL128.
The following fault message will be shown:
FAULT: Mains, ext. power supply
13. Fault output "Loss of the battery charger to external power supply
equipment" will activate a fault in EBL128. It will have the same
time delay, as set for the "Loss of main power source" fault for
58
Type of output = Routing equipment (Fire brigade tx).
EBL128 Planning Instructions V1.1.x