Panasonic EBL128 Planning Instructions page 39

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
6.1.1.6
algorithm is used to secure the smoke detection and to prevent
false (nuisance) alarms, e.g. a minimum of nine consecutive
readings over the fire alarm level are required, before the
detector goes into alarm. (One reading per sec.)
The detector has unleaded soldering.
To be plugged in a CDB 2324.
4375 Heat detector. Fixed temperature heat detector, 60°C, class
A2S (static response temp. range 54-70°C), latching.
Min./typical/max. ambient temp. -10/+25/+40°C.
The detector has unleaded soldering. Has replaced 6275.
To be plugged in a CDB 2324.
4376 Heat detector. Fixed temperature heat detector, 80°C, class BS
(static response temp. range 69-85°C), latching.
Min./typical/max. ambient temp. -10/+40/+60°C.
The detector has unleaded soldering. Has replaced 6276.
To be plugged in a CDB 2324.
6295 Heat detector: Enclosed (IP67)
heat detector, class A2 S (static response temp. range 54-70°C),
latching.
Min./typical/max. ambient temp. -40/+25/+50°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6296 Heat detector: Enclosed (IP67)
heat detector, class B S (static response temp. range 69-85°C),
latching.
Min./typical/max. ambient temp. -40/+40/+65°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6297 Heat detector: Enclosed (IP67). Fixed temperature (87°C) heat
detector, class C S (static response temp. range 84-100°C),
latching.
Min./typical/max. ambient temp. -40/+55/+80°C.
Built-in LED that is lit to indicate that the detector has
generated fire alarm. Terminals for ext. LED 2217 / 2218.
6298 Heat detector: Enclosed (IP67). Fixed temperature (117°C) heat
detector, class E S (static response temp. range 114-130°C),
latching. Min./typical/max. ambient temp. -40/+85/+110°C.
Terminals for ext. LED 2217 / 2218 (to indicate that the
detector has generated fire alarm). NOTE! No built-in LED.
Accessories
3314 Address setting tool. Is used to write or read the COM loop
units' technical address (001-127). It is also used to write or
39
As from January 2005, this detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < T
40
As from January 2005, this detector holds the ATEX classification:
Ex II 3GD EEx nA II T5 (T 100°C), -40°C < T
EBL128 Planning Instructions V1.1.x
39
. Fixed temperature (57°C)
40
. Fixed temperature (72°C)
< 50°C.
a
< 65°C.
a