Operating Instructions Fire alarm system EBL512 V2.3.x

Overview

The EBL512 system

EBL512 is a microprocessor controlled intelligent fire alarm system,
intended for analog addressable smoke detectors, as well as
conventional detectors and manual call points. Programmable control
outputs and output units are available. Up to 512 addresses can be
connected to each control unit (c.i.e.).
EBL512 is available in several types, versions and configurations. It
can be connected to a TLON network, a "system", with up to 30
control units. Each control unit has access to all information.
EBL512 is designed according to the European standard EN54, part 2
and 4. The front conforms with SS3654.

Expansion boards

In the control unit (c.i.e.) it is possible to mount up to six expansion
boards. The following types are available:
1580 8 zones expansion board
1581 8 relays expansion board
1582 External FBP interface board
1583 German FBP interface board
1584 Autronica interface board (four BS4 loops)
1587 External FBP / DU interface board
Regarding the expansion boards, see also the EBL512 Planning
Instructions and drawings.

Printer

Control unit 1549 is equipped with a printer.
In control unit 1548 it is possible to mount a 1558 Printer.

Power supply

The main power source is a built-in rectifier (1537), 230 V AC / 24 V
DC, 4.5 A.
The second power source is a backup battery (2 x 12 V). In the c.i.e.
is space for two 24-27 Ah batteries. Larger batteries (up to 60 Ah) has
to be placed outside the c.i.e.
The batteries and the rectifier are connected to the Charger board
6
(1657)
, which handles the charging of the batteries, etc. Low or High
current charging mode is selected depending on the wanted backup
3
Max. two 1582 + 1587 boards (together) per control unit.
4
Max. one 1583 board per control unit. 1583 board is not possible to use in
Swedish (SBF) convention.
5
Max. four 1584 boards per control unit. 1584 board is only possible to use
in Swedish (SBF) convention.
6
The former Charger board for EBL512 had the type no. 1557.